– 19 –
11-2-8. Operable But Abnormal
(A) No or insufficient cooling/drying
Operations
Remedies
Check items
Major possible
causes
Item by
symptom
Can the following temperature difference between
inlet and outlet air be obtained?
Not blocked.
(Cooling : 14 to 18 F)
(Drying : 23 to 27 F)
Clean the filter.
Set it to "HIGH".
Is the filter blocked?
Is the fan speed at "HIGH"?
Isn't the cooling load excessive?
Explain the running
conditions again using
the instruction manual.
Insufficient refrigerant gas?
Gas leak?
No
In case of insufficient
gas, replenishment is
according to the gas
replenish procedure.
YES
NO
YES
NO
NO
YES
Please close
the window