11-2-7. The Unit Repeats ON/OFF Operation Frequently
Operations
Remedies
Check items
Major possible
causes
Item by
symptom
YES
NO
Heat exchange of the
condenser is faulty.
Condenser (water)
Condenser (air)
Normal
Normal
Setting of the
thermostat is faulty.
Correct it.
Does the fan motor repeat
ON/OFF operation?
In case the gas temp. and
the running current are high.
Control PCB ass'y is
faulty.
Normal operation
Does the compressor repeat ON/OFF
opertion?
Over current
High
Measure the running
current.
Measure the gas
temperature.
90 C ~ 105 C
(discharge)