Check code
Main remote
controller
H08
H14
H16
Outdoor 7-segment display
Check code
H08
H14
H16
Sub-code
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
—
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
Detected
position
I/F
I/F
I/F
Check code name
Oil level detective temp
sensor error
Compressor 2 case
thermo operation
Oil level detective circuit
system error
MG-SW error
OCR operation
Status
All stop
All stop
All stop
All stop
All stop
All stop
Error detection condition
• Resistance value of sensor is
infinite or zero. (Open/Short)
• Resistance value of sensor is
infinite or zero. (Open/Short)
• Resistance value of sensor is
infinite or zero. (Open/Short)
• Resistance value of sensor is
infinite or zero. (Open/Short)
Compressor 2 case thermostat
operated.
Temperature change of TK1 could
not be detected though compressor
1 started the operation.
Temperature change of TK2 could
not be detected though compressor
2 started the operation.
Temperature change of TK3 could
not be detected though compressor
started the operation.
Temperature change of TK4 could
not be detected though compressor
started the operation, or the
difference from other TK sensor
changed for a constant time only
within the specified range.
Check item (position)
• Check connection of TK1 sensor connector.
• Check characteristics of TK1 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check connection of TK2 sensor connector.
• Check characteristics of TK2 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check connection of TK3 sensor connector.
• Check characteristics of TK3 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check connection of TK4 sensor connector.
• Check characteristics of TK4 sensor resistance value.
• Check outdoor P.C. board (I/F) error.
• Check compressor 2 case thermo circuit. (Connector, cable, P.C. board)
• Check full opening of service valve. (Gas and liquid side)
• Check outdoor PMV clogging. (PMV1, 2)
• Check SV42 valve leak.
• Check miscabling/misinstallation of SV41 and SV42.
• Check valve opening of indoor PMV.
• Check refrigerant shortage.
• Check compressor error.
• Check TK1 sensor coming-off.
• Check characteristics of TK1 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check operation error of SV3E valve.
• Check capillary clogging of oil-equation circuit and operation error of stop valve.
• Check refrigerant stagnation in compressor.
• Check MG-SW or OCR.
• Check TK2 sensor coming-off.
• Check characteristics of TK2 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check SV3E valve operation.
• Check capillary clogging of oil equalization circuit and check stop valve operation.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
• Check TK3 sensor coming-off.
• Check characteristics of TK3 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check SV3E valve operation.
• Check capillary clogging of oil-equalization circuit and check valve operation.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
• Check TK4 sensor coming-off.
• Check characteristics of TK4 sensor resistance value.
• Check TK1, TK2, TK3, and TK4 misconnection.
• Check SV3E valve operation.
• Check capillary clogging of oil-equalization circuit and check valve operation.
• Check refrigerant stagnation in compressor shell.
• Check MG-SW or OCR.
MG-SW : Magnet Switch
OCR
: Over-current Relay