– 72 –
Check code display
L04
L06
L08
L10
L28
L29
L30
P03
P05
P07
P10
P13
P15
P17
P19
P20
Outdoor 7-segment
Sub-code
—
No. of indoor units with priority
([L05/L06] by single display)
—
—
—
01: A3-IPDU1 error
02: A3-IPDU2 error
03: A3-IPDU1/2 error
04: Fan IPDU error
05: A3-IPDU1 + Fan IPDU error
06: A3-IPDU2 + Fan IPDU error
07: All IPDU error
Detection of indoor unit No.
—
01: Detection of open phase
02: Over-voltage
01: Compressor 1 side
02: Compressor 2 side
Detection of indoor unit No.
—
01: TS condition
02: TD condition
—
Detection of outdoor unit No.
—
TCC-LINK central
&
Remote controller
L04
L05
L06
(L08)
L10
L28
L29
(L30)
P03
P05
P07
(P10)
P13
P15
P17
P19
P20
Representative defective position
Duplication of outdoor line addresses
Duplicated indoor units with priority
(Displayed in indoor unit with priority)
Duplicated indoor units with priority (Displayed
on the unit other than indoor unit with priority)
Indoor group address unset
Outdoor capacity unset
Quantity over of connected outdoor units
No. of IPDU error
There is abnormal external input of indoor /
outdoor units (Interlock)
Outdoor discharge (TD1) temp error
Detection of open phase/
Detection of open phase (Incorrect phase)
Heat sink overheat error
Overflow is detected in an indoor unit.
Outdoor liquid back detection error
Gas leak detected
Outdoor discharge (TD2) temp error
4-way valve reversal error
High-pressure protective operation
Error contents
Line address setup is duplicated against outdoor unit in
different refrigerant pipe line.
There are multiple indoor units with priority
(against indoor unit with priority)
There are multiple indoor units with priority
(against indoor unit without priority)
Indoor unit whose indoor group address is unset exists.
(Detected also at indoor unit side)
Capacity of outdoor unit is not set up.
(Replace service P.C. board with a new one.)
No. of connected outdoor units exceeds 4 units.
No. of IPDU (PC board) in inverter box is few.
There is indoor unit which stops abnormally by external
error input in one line. (
←
Detected by indoor unit)
High temperature error is detected on discharge temp
sensor (TD1).
Open phase/Phase order to motor is incorrect.
Motor may not rotate clockwise, or may not rotate.
High temp error is detected on temp sensor (TH) built in
outdoor IGBT
There is indoor unit which stops abnormally by detection
of overflow in one line. (
←
Detected by indoor unit)
It is judged as liquid back occurred from refrigerating
cycle status.
Continuation of high temperature of outdoor suction temp
sensor (TS1) over reference value is repeatedly detected.
High temperature error is detected on discharge temp
sensor (TD2)
Refrigerating cycle error is detected in heating operation.
High-pressure (Pd) sensor detects value over reference
value.
Check code display
F13
H01
H02
H03
P04
P22
P26
P29
Outdoor 7-segment
Sub-code
01: Compressor 1 side
02: Compressor 2 side
01: Compressor 1 side
02: Compressor 2 side
01: Compressor 1 side
02: Compressor 2 side
01: Compressor 1 side
02: Compressor 2 side
01: Compressor 1 side
02: Compressor 2 side
04: rpm difference error
06: Max. rpm over
08: Out of order
0A: Idc operation
0C: Air flow lock
0d: Lock
0E: Synchronization error
0F: Control error
01: Compressor 1 side
02: Compressor 2 side
01: Compressor 1 side
02: Compressor 2 side
TCC-LINK central
&
Remote controller
F13
H01
H02
H03
P04
P22
P26
P29
Representative defective position
Error of temp sensor (TH) built in outdoor IGBT
Compressor break down
Compressor error (Lock)
Current detection circuit error
High pressure SW system operation
IPDU error for outdoor fan
G-Tr (IGBT) short-circuit protection error
Compressor position detection circuit system error
Error contents
Open/Short of temp sensor (TH) built in outdoor IGBT is
detected.
Detection circuit of inverter current (Idc) detects
over-current.
Compressor lock is detected.
Abnormal current is detected during stop of compressor.
High pressure SW operates.
IPDU for outdoor fan detects each error.
Short-circuit protection operation (Momentary over-current)
of compressor motor drive circuit element works.
Position detection error of compressor motor is detected.
NOTE)
Even the same error contents such as communication error, the check codes display may differ according to the detected device.
In case of check code detected by a central controller of the remote controller, it does not exactly have direct influence to operation of the air conditioner.