Setting of indoor air conditioner in “Specific indoor air conditioner priority” mode
Change the setting during stop of the system. (Be sure that setting is performed during stop of the system.)
Procedure
1
2
3
4
5
6
Operation contents
Push
SET
+
CL
+
TEST
buttons concurrently for 4 seconds or more.
After some time, the display part flashes as shown below.
Check the displayed item code is [10].
• When the displayed item code is other than [10], push
TEST
button to
erase the display and then start from the first step.
(The operation from the remote controller is not accepted for approx. 1 minute after pushing
TEST
button.)
(In group control, the firstly displayed indoor air conditioner No. becomes master unit.)
Every pushing
UNIT
button, the indoor air conditioner No. in the group control is displayed one by one.
Select an indoor air conditioner of which setting is changed.
In this time, the location of the indoor air conditioner of which setting is changed can
be confirmed because fan and flap of the selected indoor air conditioner operate.
Using the setting temperature
/
buttons, specify the item
code [04].
Using the timer time
/
buttons, select the setting data [0001].
Priority: 0001, Without priority: 0000
Push
SET
button. When the display changed from flashing to lighting, the setting finished.
After finish of setting, push
TEST
button. (Setting has determined.)
When pushing
TEST
button, the display disappears and the status
enters in the normal stop status.
(After pushing
TEST
button, operation from the remote controller is
nor accepted for approx. 1 minute.)
6
5
3
2
4
1
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C.
No.
(NOTE)
Only one indoor air conditioner can be set to “With priority”. When multiple indoor air conditioners are set to
“With priority” in mistake, an error code (L05 or L06 : Indoor air conditioners priority duplicated) is displayed on
the remote controller.
For the unit displaying “L05”, [
(With priority)] is set up. Leave one air conditioner to give priority among
the indoor air conditioners displayed with “L05” and then return setup data of the other air conditioners to
[
(No priority)].
Error code
L05
L06
Error contents
Indoor air conditioners priority duplicated ([
] is set up.)
Indoor air conditioners priority duplicated ([
] is set up.)