85
–
Error detected by TCC-LINK central control device
Check code
Display on central
control device
C05
C06
C12
P30
Outdoor 7-segment display
Check code
Sub-code
—
—
—
—
—
Differs according to
error contents of the with alarm
—
—
Detected
position
TCC-LINK
—
General-
purpose device
I/F
TCC-LINK
—
Check code name
TCC-LINK central control device
transmission error
TCC-LINK central control device
receiving error
Interface batch alarm of general-
purpose control devices
Follower unit error of group control
Duplicated central control address
Status
Operation
continued.
Operation
continued.
Operation
continued.
Operation
continued.
Operation
continued.
Error detection condition
Signal is not transmit from central
control device.
Signal is not received from central
control device.
Error was input in general-purpose
control device control interface.
An error occurred in follower unit of the
group control. ([P30] is displayed only
on the central control remote controller.)
Central control addresses were
duplicated.
Check item (position)
• Check central control device error.
• Check communication line error of central control device.
• Check setup of end terminal resistance.
• Check central control device error.
• Check communication line error of central control device.
• Check setup of end terminal resistance.
• Check the power of connecting destination connected device.
• Check P.C. board error of the connected device.
• Check error input.
• Check the check code of the unit with alarm.
• Check the address setup.