– 25 –
4
INSTALLATION OF INDOOR UNIT
WARNING
Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible.
If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than specified.
External view
Installing the four 10mm-diameter hanging bolts
• Space the hanging bolts according to the dimensions shown in the diagrams below.
• Use 10mm-diameter hanging bolts (Required at the site).
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
16
120
4
2.7
120
• Wired remote controller (RBC-AMT31E)
Mounting of the remote controller (Sold separately)
For mounting of the remote controller, refer to the Installation manual attached to the remote controller.
• Do not place the remote controller in the direct sunlight or at place near a heater.
Model MMD-
AP0481HFE
AP0721HFE
AP0961HFE
A
B
C
D
892
810
Ø9.5 flare
Ø15.9 flare
1392
1260
Ø12.7 flare
Ø22.2 brazing
Considering piping and wire connecting works in the
ceiling after hanging down the indoor unit, select an
installation place and then determine the drawing-out
direction of the pipes.
• If the ceiling has been already set, draw the
refrigerant pipe, drain pipe, inter-unit wire between
indoor and outdoor units, central control system
wire and remote controller cord up to the positions
where pipes and wires are connected before
hanging down the indoor unit.
• Install the indoor unit/outdoor unit and also arrange
the power supply wiring, connecting wiring and
remote controller wiring 1m apart from the television
and the radio in order to avoid image turbulence
and noise.
1288 (Hanging bolt pitch)
1328
100
B
(Hanging bolt pitch)
A
4-M10 hanging bolt
(Local procure)
Electrical
parts box
1262
704
850
492
216
150
47
61
Drain pipe connecting port
60
23
Refrigerant pipe connecting port
(Gas side) D
Refrigerant pipe connecting port
(Liquid side) C