JKSSS+ Series - 67
JKSSS+ Series
2.3 - 4.2KV
SP.12 System Setpoints (Setpoint Page 12)
(Security Level: 3)
MENU
PAGE 12 SYSTEM
SETPOINTS
DEFAULT DISPLAY
SCREEN
(Hit DOWN ARROW eleven times)
METERING DATA
PAGE #: 1
Enter Metering Page (1 - 4)
Number for display
METERING DATA
SCREEN #: 1
ALARMS
THERMAL REGISTER
SETUP INFORMATION
PRESS ENTER TO CLR
THERMAL REGISTER
RTD FAILURE ALARM
ALARM: DISABLED
THERMAL REGISTER
ALARM: 90%
HOT STALL TIME
: 1/2 O/L CLASS
STOPPED COOL DOWN
TIME: 30 MIN
RUNNING COOL DOWN
TIME: 15 MIN
COLD STALL TIME
: O/L CLASS
RELAY MEASURED COOL
RATES: DISABLED
Enabled or Disabled
Range:
Off, 40 - 95%
Increments of 1
Range:
O/L CLASS,
4 - 40 SEC
Increments of 1
Range:
1/2 O/L CLASS,
4 - 40 SEC
Increments of 1
Range:
10 - 300 MIN
Increments of 1
Range:
10 - 300 MIN
Increments of 1
Range:
ENABLED or
DISABLED
THERMAL ALARM
DELAY: 10 SEC.
Range:
1 - 20 SEC.
Increments of 1
Enter Metering
Screen Number for display
MOTOR DESIGN AMBIENT
TEMPERATURE: 40 C
MOTOR DESIGN RUN
TEMPERATURE: 80% MAX
MOTOR STATOR MAX
TEMPERATURE: INS CLS
THERMAL REGISTER
MINIMUM: 15%
I/B INPUT TO THERMAL
REGISTER: ENABLED
Range:
10 - 50%, OFF
Increments of 1
Range:
10 - 90 C
Increments of 1
Range: 50 - 100% of Motor
Stator Max Temp.
Increments of 1%
Range:
Insulation Class
10 - 240 C
Increments of 1
Options:
ENABLED or
DISABLED
USE CALCULATED K OR
ASSIGN: 7
Range:
1 - 50, ON
Содержание JKSSS Plus Series
Страница 2: ......
Страница 6: ...Reference Chart ...
Страница 45: ...JKSSS Series 39 JKSSS Series 2 3 4 2KV 5 1 5 Relay Configuration Setpoint Page 5 ...
Страница 90: ...JKSSS Series 84 JKSSS Series 2 3 4 2KV 7 3 Overload Curve Definition ...
Страница 92: ...JKSSS Series 86 JKSSS Series 2 3 4 2KV 7 5 Typical Wiring Diagram ...
Страница 93: ...JKSSS Series 87 JKSSS Series 2 3 4 2KV ...
Страница 95: ...JKSSS Series 89 JKSSS Series 2 3 4 2KV ...