JKSSS+ Series - 8
JKSSS+ Series
2.3 - 4.2KV
1.6 General Protection
The soft starter is provided with a built-in motor protection relay that can be
programmed for primary protection of the motor/load system. Operation of the soft
starter can be divided into 4 modes; Ready, Start, Run and Stop.
Ready Mode:
In this mode, control and line power are applied and the starter is
ready for a start command. Protection during this mode includes the monitoring
of current for leakage through multiple shorted SCRs or welded contacts on the
Bypass Contactor. Other protection features in effect are:
· Starter Temperature
· Shorted SCR
· Phase Reversal (if enabled)
· Line Frequency Trip Window
· External Input Faults
Note:
The “Programming Mode” can only be entered from the Ready Mode.
During programming, all protection features and start command are disabled.
Start Mode:
These additional protection functions are enabled when the soft
starter receives a valid Start command:
· Phase Reversal (if enabled)
· Start Curve
· Acceleration Timer
· Phase Imbalance
· Short Circuit / Load Pre-check (Toe-in-the-Water)
· Ground Fault (Optional)
· External Input Faults
· Accumulated Starting FLA Units (I
2
t Protection)
· Overload Protection
· Thermal Capacity
Note:
Shorted SCR and Shunt Trip protection are no longer in effect once the
soft starter goes into the Start Mode.
Run Mode
: The soft starter enters the Run Mode when it reaches full output
voltage
and
the motor current drops below the FLA setting (motor nameplate
FLA plus service factor) for a predetermined period of time. During the Run Mode
these additional protection features are enabled:
· Running Overload Curve
· Phase Loss
· Under Current / Load Loss
· Over Current / Electronic Shear Pin (Jam protection)
· External Input Faults
Stop Mode
: Once a Stop command has been given, the protection features
change depending on which Stop Mode is selected.
·
Decel Mode:
Retains all protection features of the Run Mode. At the end of
Decel, the motor will be stopped and the protection features change as
indicated below.
Содержание JKSSS Plus Series
Страница 2: ......
Страница 6: ...Reference Chart ...
Страница 45: ...JKSSS Series 39 JKSSS Series 2 3 4 2KV 5 1 5 Relay Configuration Setpoint Page 5 ...
Страница 90: ...JKSSS Series 84 JKSSS Series 2 3 4 2KV 7 3 Overload Curve Definition ...
Страница 92: ...JKSSS Series 86 JKSSS Series 2 3 4 2KV 7 5 Typical Wiring Diagram ...
Страница 93: ...JKSSS Series 87 JKSSS Series 2 3 4 2KV ...
Страница 95: ...JKSSS Series 89 JKSSS Series 2 3 4 2KV ...