JKSSS+ Series - 36
JKSSS+ Series
2.3 - 4.2KV
5.1 Setpoints Page List
These charts list the Setpoint Page, the programmable functions and the section.
5
.1.1 Basic Configuration (Setpoint Page1)
5.1.2 Starter Configuration (Setpoint Page 2)
Chapter 5 - Setpoint Programming
The
JKSSS+ Series
has thirteen programmable setpoint pages which define the
motor data, ramp curves, protection, I/O configuration and communications. In Section
5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages
are illustrated and defined for easy navigation and programming. Note: Setpoints can
only be changed when the starter is in the Ready Mode. Also the soft start will not start
when it is in programming mode.
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Start Control Mode
Start Ramp 1
Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp,
Tach Ramp
SP2.1
Jog Voltage
50%
5-75%, Off
SP2.2
Start Ramp #1 Type
Voltage
Current, Voltage
Initial Voltage #1
20%
0-100%
Ramp Time #1
10 sec
0-120 sec
Current Limit #1
350% FLA
200-500 %
Initial Current #1
200% FLA
0-300%
Ramp Time #1
10 sec
0-120 sec
Maximum Current #1
350% FLA
200-500 %
Start Ramp #2 Type
Disabled
Current, Voltage, Disabled
Initial Voltage #2
60%
0-100 %
Ramp Time #2
10 sec
0-120 sec
Current Limit #2
350 % FLA
200-500 %
Initial Current #2
200% FLA
0-600 %
Ramp Time #2
10 sec
0-120 sec
Maximum Current #2
350% FLA
200-500 %
Kick Start Type
Disabled
Voltage or Disabled
Kick Start Voltage
65%
10-100 %
Kick Start Time
0.50 sec
0.10-2.00
Deceleration
Disabled
Enabled or Disabled
Start Deceleration Voltage
60%
0-100 %
Stop Deceleration Voltage
30%
0-59 %
Deceleration Time
5 sec
1-60 sec
Timed Output Time
Off
1-1000 sec, Off
SP2.7
Run Delay Time
1 Sec
1-30 sec, Off
SP2.8
At Speed Delay Time
1 Sec
1-30 sec, Off
SP2.9
SP2.3
SP2.4
SP2.5
SP2.6
Page
2
Starter Configuratio
n
Level
1
No Passowrd Require
d
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Motor Full Load Amps (FLA)
Model dependent
50 - 100% of Unit Max Current Rating
(Model and Service Factor dependent)
SP1.1
Service Factor
1.15
1.00 – 1.3
SP1.2
Overload Class
10
O/L Class 5-30
SP1.3
NEMA Design
B
A-F
SP1.4
Insulation Class
B
A, B, C, E, F, H, K, N, S
SP1.5
Line Voltage
Model dependent
1000 to 7200V
SP1.6
Line Frequency
60
50 or 60 HZ
SP1.7
Page
1
Basic Configuration
Level
1
No Passowrd Require
d
Содержание JKSSS Plus Series
Страница 2: ......
Страница 6: ...Reference Chart ...
Страница 45: ...JKSSS Series 39 JKSSS Series 2 3 4 2KV 5 1 5 Relay Configuration Setpoint Page 5 ...
Страница 90: ...JKSSS Series 84 JKSSS Series 2 3 4 2KV 7 3 Overload Curve Definition ...
Страница 92: ...JKSSS Series 86 JKSSS Series 2 3 4 2KV 7 5 Typical Wiring Diagram ...
Страница 93: ...JKSSS Series 87 JKSSS Series 2 3 4 2KV ...
Страница 95: ...JKSSS Series 89 JKSSS Series 2 3 4 2KV ...