JKSSS+ Series - 21
JKSSS+ Series
2.3 - 4.2KV
Controller used as service equipment for an ungrounded system or as a main section for a separately derived
system.
a. A grounding electrode conductor (ground wire) sized in accordance with NEC 250 should be run from the
grounding electrode to the controller ground bus or ground terminal.
b. If the system is grounded at any point ahead of the controller, the grounded conductor should be run to the
controller in accordance with NEC 250 and connected to the ground bus or ground terminal.
c. Steps (a) and (b) should effectively connect together the grounding electrode, the controller frame, all outgoing
equipment grounding connectors and any grounded conductor which runs to the controller.
Controller not used as service equipment or as a main section for a separately derived system, and used on either
a grounded or ungrounded system:
a. The controller frame and any ground bus should be grounded by means of equipment grounding conductors
having a size in accordance with NEC 250 and run with the main supply conductors or by bonding to the
raceway enclosing the main supply conductors in accordance with NEC 250.
b. Ground leads should be connected to cable potheads/shields as specified by the manufacturer of these de
-
vices.
Fig. 7 Ground Bus Splice
Содержание JKSSS Plus Series
Страница 2: ......
Страница 6: ...Reference Chart ...
Страница 45: ...JKSSS Series 39 JKSSS Series 2 3 4 2KV 5 1 5 Relay Configuration Setpoint Page 5 ...
Страница 90: ...JKSSS Series 84 JKSSS Series 2 3 4 2KV 7 3 Overload Curve Definition ...
Страница 92: ...JKSSS Series 86 JKSSS Series 2 3 4 2KV 7 5 Typical Wiring Diagram ...
Страница 93: ...JKSSS Series 87 JKSSS Series 2 3 4 2KV ...
Страница 95: ...JKSSS Series 89 JKSSS Series 2 3 4 2KV ...