JKSSS+ Series - 61
JKSSS+ Series
2.3 - 4.2KV
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)
SP7.1
Setpoint Page 7 allows the user to custom design
the acceleration curve (start curve) to the specific
application. The user can custom design up to
three different curves in the soft starter. Only one
curve can be active (enabled) at a time. Each of
the three curves has eight voltage levels, with
corresponding ramp times and a current limit
setting.
Note: Each successive voltage level must be
programmed to a voltage level equal to or greater
than the previous level. All eight levels of voltages
must be programmed and the eighth level has
been preset at 100%.
•
If Custom Accel Curve has been set to curve A, B
or C on this page, the soft starter will override the
Start Control Mode selected in Setpoint Page 2,
(even if Start Control Mode in Setpoint Page 2 has
not been set to Custom Accel Curve).
Note:
Setpoint Page 7 has a security level 3
requirement.
CURVE C VOLTAGE
LEVEL 6: 67%
CURVE C VOLTAGE
LEVEL 7: 82%
CURVE C RAMP
TIME 7: 2 SEC.
CURVE C VOLTAGE
LEVEL 8: 100%
CURVE C RAMP
TIME 6: 2 SEC.
CURVE C CURRENT
LIMIT: 350% FLA
CURVE C RAMP
TIME 8: 2 SEC.
Range:
0 - 100%
Increments of 1
Range:
1 - 60 SEC
Increments of 1
Range:
0 - 100%
Increments of 1
Range:
1 - 60 SEC
Increments of 1
Range:
0 - 100%
Increments of 1
Range:
1 - 60 SEC
Increments of 1
Range:
200 - 600%
Increments of 10
CUSTOM CURVE C
Содержание JKSSS Plus Series
Страница 2: ......
Страница 6: ...Reference Chart ...
Страница 45: ...JKSSS Series 39 JKSSS Series 2 3 4 2KV 5 1 5 Relay Configuration Setpoint Page 5 ...
Страница 90: ...JKSSS Series 84 JKSSS Series 2 3 4 2KV 7 3 Overload Curve Definition ...
Страница 92: ...JKSSS Series 86 JKSSS Series 2 3 4 2KV 7 5 Typical Wiring Diagram ...
Страница 93: ...JKSSS Series 87 JKSSS Series 2 3 4 2KV ...
Страница 95: ...JKSSS Series 89 JKSSS Series 2 3 4 2KV ...