JKSSS+ Series - 46
JKSSS+ Series
2.3 - 4.2KV
SP.1 Basic Configuration (Setpoint Page 1)
In Setpoint Page 1, the starter is looking for the following basic
nameplate data of the motor.
SP1.1 Motor Full Load Amps:
Allows the user to enter the motor’s
FLA rating. Range of adjustment is 50 - 100% (less
programmed service factor).
SP1.2 Service Factor
: Sets the pickup point on the overload curve
as defined by the programmed motor full load current. Ex:
If the motor FLA is 100 and the service factor is 1.15, the
overload pickup point will be 115 Amps.
SP1.3 Overload Class:
Choose the motor protection overload class,
range from 5-30.
Ex: Overload Class 10 will trip in 10 seconds at six times
FLA.
SP1.4 NEMA design:
The motor design maximum allowed slip
(Select from Class A through F).
SP1.5 Insulation Class:
The motor insulation temperature class
(Select A, B, C, E, F, H, K, N or S).
SP1.6 Line Voltage Input:
Applied Voltage
SP1.7 Line Frequency:
The user may choose either 50 Hz or 60
Hz.
MENU
PAGE 1 BASIC
CONFIGURATION
MOTOR FULL LOAD AMPS
: 200 AMPS
SERVICE FACTOR
: 1.15 X FLA
OVERLOAD
CLASS: 10
NEMA
DESIGN: B
INSULATION
CLASS: B
LINE VOLTAGE
INPUT: 4160 VOLTS
Range:
50 - 100% of Unit
MAX CURRENT AMPS
Increments of 1
Range:
1.00 - 1.3
Increments of 0.01
Range:
5 - 30
Increments of 5
Range:
A - F
Range:
A - S
Range:
100 - 7200
LINE FREQUENCY
HZ: 60
Range:
50 or 60
Содержание JKSSS Plus Series
Страница 2: ......
Страница 6: ...Reference Chart ...
Страница 45: ...JKSSS Series 39 JKSSS Series 2 3 4 2KV 5 1 5 Relay Configuration Setpoint Page 5 ...
Страница 90: ...JKSSS Series 84 JKSSS Series 2 3 4 2KV 7 3 Overload Curve Definition ...
Страница 92: ...JKSSS Series 86 JKSSS Series 2 3 4 2KV 7 5 Typical Wiring Diagram ...
Страница 93: ...JKSSS Series 87 JKSSS Series 2 3 4 2KV ...
Страница 95: ...JKSSS Series 89 JKSSS Series 2 3 4 2KV ...