HX7+ ASD Installation and Operation Manual
179
Analog 1 Terminal Adjustment
Program
Meter Terminal Adjustment
Analog 1
This parameter adjusts the coefficient of the
Analog 1
circuit to obtain an
output that corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
Direct Access Number — F673
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
Analog 2 Terminal Setting
Program
Meter Terminal Adjustment
Analog 2
This parameter sets the
Analog 2
multifunction programmable terminal to 1 of
33 possible functions and is available on the
ASD Multicom
option board only.
Possible assignments for this output terminal are listed in
.
Direct Access Number — F674
Parameter Type —
Selection List
Factory Default —
Post-compensation
Frequency
Changeable During Run —
Yes
Analog 2 Terminal Adjustment
Program
Meter Terminal Adjustment
Analog 2
This parameter adjusts the coefficient of the circuit to obtain an output that
corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
Direct Access Number — F675
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
FP Terminal Setting
Program
Terminal Selection
FP
This parameter commands the multifunction programmable
FP
terminal to
monitor the value of 1 of 33 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the
FP
output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the
FP
output.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for this output terminal are listed in
.
Direct Access Number — F676
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
FP Terminal Adjustment
Program
Terminal Selection
FP
This parameter sets the full-scale reading of the
FP Terminal
. The full-scale
reading of the monitored variable selected in
may be set here.
Direct Access Number — F677
Parameter Type —
Numerical
Factory Default —
3.840
Changeable During Run —
Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Display Units for Voltage and Current
Program
Utility Parameters
Display Units
This parameter sets the unit of measurement for current and voltage values
displayed on the keypad.
Settings:
0 — %
1 — V/A
Direct Access Number — F701
Parameter Type —
Selection List
Factory Default — %
Changeable During Run —
Yes
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...