6
HX7+ ASD Installation and Operation Manual
Protection
•
Ensure that primary protection exists for the input wiring to the equipment. This protection must be
able to interrupt the fault current from the power line. The equipment may or may not be equipped
with an input disconnect (option).
•
All cable entry openings must be sealed to reduce the risk of entry by vermin and to allow for
maximum cooling efficiency.
•
External dynamic braking resistors must be thermally protected.
•
If the ASD is supplied with a motor as a package, it then becomes a machine and has to meet the
Essential Health and Safety Requirements of the EU Machinery Directive, 2006/42/EC. It is also a
requirement that the system have an
Emergency Off
function that meets the requirements of EN
ISO 13850:2008, and that any local or regional requirements must be met.
•
It is the responsibility of the ASD installer/maintenance personnel to set up the
Emergency Off
braking system of the ASD. The function of the
Emergency Off
braking function is to remove
output power from the ASD in the event of an emergency. A supplemental braking system may also
be engaged in the event of an emergency.
For further information on braking systems, see
.
Note:
A supplemental emergency stopping system should be used with the ASD. Emergency
stopping should not be a task of the ASD alone.
•
Follow all warnings and precautions and do not exceed equipment ratings.
Dynamic Braking Resistor Requirements
When using a
Dynamic Braking Resistor
(DBR), use thermal protection and an input contactor that
will open the input 3-phase power circuit to the ASD in the event that a DBR over-temperature
condition occurs. In the event of a power source over-voltage condition or an ASD failure, the input
contactor will prevent hazardous DBR temperatures.
Dynamic Braking Resistors
shall be connected across terminals
PA
and
PB ONLY
(when used).
Connecting a
Dynamic Braking Resistor
elsewhere may cause a fire.
Heavy duty DBRs shall be wired using the same gauge wire as the motor leads. Light duty DBRs may
use one wire size smaller (AWG) than the motor leads.
The total wire length from the ASD to the DBR shall not exceed ten feet.
Because the heat generated by the DBR will affect the cooling capacity of the ASD heat sink, the
resistor pack shall be mounted above or to the side of the ASD —
Never below the ASD
. Maintain a
minimum of six inches between the resistor pack and the ASD unit.
If EMI/RFI noise is of concern, the DBR wiring shall be three-core screened cable. The screen shall
connect to the ASD enclosure and the resistor enclosure.
DANGER
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...