84
HX7+ ASD Installation and Operation Manual
Motorized Pot Frequency at Power Down
Program
Frequency Setting
Motorized Pot
When the
Frequency Mode #1 Selection
(
) setting is set to
Use MOP
Function Simulation
, this parameter determines the outcome of the
Frequency
Mode #1
setting at powerdown or stop.
Settings:
0 — Erase
1 — Store
If
Erase
is selected, the ASD will
not
store the frequency setpoint and
establishes a setpoint of 0.0 Hz when restarted.
If
Store
is selected, the ASD will maintain the current frequency setpoint in
memory while stopped, during fault conditions, or when power is removed.
This setpoint will be used as the initial frequency setpoint when the ASD is
restarted.
A control terminal configured as
MOP Frequency Clear
will establish a
frequency setpoint of 0.0 Hz regardless of the
Motorized Pot Frequency at
Power Down
setting.
Direct Access Number — F108
Parameter Type —
Selection List
Factory Default —
Erase
Changeable During Run —
No
ON Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the virtual input terminal
ON
. As a
virtual terminal, the
ON
control terminal exists only in memory and is
considered to always be in its
True
(or connected to
CC
) state.
It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable
ON
terminal to 1 of the 68 possible
Direct Access Number — F110
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
F Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
F
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
F
terminal to 1 of the 68 possible
Direct Access Number — F111
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
R Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
R
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
R
terminal to 1 of the 68 possible
Direct Access Number — F112
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...