Submenu settings
Service monitor
• The temperature of the sensor is displayed on the
remote control.
• This function can be used to check whether the
sensor is correctly installed.
(1) Press the [
] / [
] button to select "Service
monitor" on the "Submenu settings" screen, then press
the [ ] button.
(2) Press the [ ] button to select the unit, then press the
[ ] button to display the status.
Hydro unit data
Code
Data designation
Unit
00
Control temperature (hot water cylinder)
°C
01
Control temperature (Zone 1)
°C
02
Control temperature (Zone 2)
°C
03
Remote control sensor temperature
°C
04
Condensation temperature (TC)
°C
06
Water inlet temperature (TWI)
°C
07
Water outlet temperature (TWO)
°C
08
Water heating outlet temperature (THO)
°C
09
Floor input temperature (TFI)
°C
0A
Hot water cylinder temperature (TTW)
°C
0B
Position of the mixing valve
Step
0E
Low pressure (Ps) x 100
MPa
0F
Hydro Soft Ver.
-
Outdoor unit data
Code
Data designation
Unit
60
Heat exchange temperature (TE)
°C
61
Outdoor air temperature (TO)
°C
62
Drain temperature (TD)
°C
63
Intake temperature (TS)
°C
65
Heat sink temperature (THS)
°C
6A
Current x 10
A
6D
Temperature of the heat exchanger coil (TL)
°C
70
Compressor operation Hz
Hz
72
Number of revolutions of the outdoor fan (low or
model with 1 fan)
rpm
73
Number of revolutions of the outdoor fan (high)
rpm
74
Outdoor PMV position x 1/10
pls
7A
Discharge pressure (PD) x 1/10
kPa
Hydro unit data
Code
Data designation
Unit
F0
Microprocessor-supplied
accumulation time x 1/100
h
F1
Domestic hot water compressor ON
accumulation time x 1/100
h
F2
Cooling water compressor ON
accumulation time x 1/100
h
F3
Heating compressor ON
accumulation time x 1/100
h
F4
Operation of integrated WS pump
accumulation time x 1/100
h
F5
Accumulation time for operation of domestic hot
water cylinder heating x 1/100
h
F6
Accumulation time for operation of auxiliary
heating x 1/100
h
F7
Accumulation time for operation of
additional heating x 1/100
h
• Some sensors (temperature/pressure) are not
displayed as these are not connected.
Submenu settings (2/2)
Service monitor
DN for hydro unit
DN for remote control
Reset current consumption data
Sensor information
Confirm
Service monitor
1 - 1
1 - 4
1 - 7
1 - 2
1 - 5
1 - 8
1 - 3
1 - 6
Unit
Confirm
Service monitor
Code
Data
00
0024
Back
SER
VICE MONITOR
Top screen
Press [
Menu ] + [
]
at the same time (4 s)
Содержание ESTIA R32 HWT-1101F21MT6W-E
Страница 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Страница 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Страница 8: ......
Страница 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Страница 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Страница 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Страница 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Страница 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Страница 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Страница 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Страница 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Страница 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Страница 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Страница 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Страница 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Страница 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Страница 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...