Fault detection via water-to-air heat exchanger or outdoor unit
O ........ Possible
X ........ Not possible
Error
Code
Diagnostics of functional operation
Determination and measures
Technical cause
Backup
present
Automatic
reset
A01
Pump or flow volume error
1. Determined by TC sensor
TC≥63°C was detected in heating or hot
water supply heat pump operation
(except for defrosting)
Heating
X
Hot water
O
X
Hardly any or low water flow rate
- Insufficient air supply
- Blockage due to dirt in water pipe system
- The water pipe is too long
- Installation of a buffer tank and a secondary
pump
2. Detected by flow switch deviation
In no signal from the flow switch is
displayed 2 minutes after the installed
pump starts
3. Detection of excessive rattling at the flow
switch input
Detection of rattling:
Detects changes at the input (OFF
ON)
4 times within 10 seconds during operation
4. Removal of the flow switch connection
If the stopped installed pump starts
operation, the flow switch status "Water
flow" is detected
1. Removal of the flow switch connection
2. Flow switch defect
A02
Water temperature increase error
(heating)
If one of the TWI, TWO, and THO sensors
reaches 70°C
Heating
X
Hot water
O
O
1. Check water inlet, water outlet, and heating
outlet sensors (TWI, TWO, THO)
2. Backup heater defect
(defective thermostat for automatic reset)
A03
Temperature increase error
(hot water preparation)
If the TTW sensor reaches 85°C
Heating
O
Hot water
X
O
1. Check the hot water cylinder sensor (TTW)
2. Check the hot water cylinder thermo cut-out
A04
Frost protection mode
(1)
1. TWO>20°C:
2xTC+TWO≤-12°C detected
2. TWO≤20°C:
TC+TWO≤4°C detected
3. TWI≤10°C detected during defrosting
O
X
1. Hardly any or low water flow rate
- Blockage due to dirt in water pipe system
- The water pipe is too long or short
2. Check the heating circuit
- Power supply voltage, cut-out, power supply
connection
3. Apply the setting for the backup heater
4. Check water inlet, water outlet, heat exchanger
sensors (TWI, TWO, TC), and flow switch
A05
Piping frost protection mode
Activation of the heating if TWO<4 or TWI<4
or THO<4 and after 30 minutes not TWO,
TWI, THO≥5°C
O
O
1. Check the heating circuit
- Power supply voltage, cut-out, power supply
connection
2. Check water inlet, water outlet, and heating
outlet sensors (TWI, TWO, THO)
3. Disconnection of the backup heater
A07
Pressure switch operation
The pressure switch works continuously
for 300 seconds while the heat pump is in
operation
O
X
1. Hardly any or low water flow rate
2. Flow switch defect
3. Under-load operation under the above conditions
4. Pressure switch defect
A07
HI POWER
Combined fault
Model name of the Hydrobox is different
O
X
Check whether DP_SW13_4 is set to "ON"
FAUL
T SYMPTOMS
Содержание ESTIA R32 HWT-1101F21MT6W-E
Страница 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Страница 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Страница 8: ......
Страница 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Страница 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Страница 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Страница 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Страница 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Страница 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Страница 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Страница 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Страница 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Страница 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Страница 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Страница 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Страница 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Страница 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...