TOSHIBA
I 23
TOSHIBA
I 23
Maximum heating capacity and power consumption
HWT-1101H(R)W-E
Power (kW)
VLT (°C)
30
35
40
45
50
55
60
65
TO (°C)
-25
5.12
5.20
5.28
5.36
5.35
5.33
5.06
--
-20
6.21
6.29
6.36
6.25
6.26
6.07
5.58
--
-15
7.30
7.37
7.45
7.52
7.17
6.81
6.10
--
-10
8.70
8.45
8.27
8.10
7.62
7.15
6.67
--
-7
9.56
9.10
8.77
8.44
7.86
7.35
7.01
--
-2
10.65
10.28
10.16
10.03
9.41
8.79
7.78
--
2
11.95
11.46
11.06
10.66
10.08
9.50
8.40
--
7
14.01
13.24
12.83
12.41
11.29
10.17
9.05
5.08
10
14.62
13.86
13.39
12.92
11.88
10.84
9.80
5.09
12
15.03
14.28
13.77
13.26
12.28
11.29
10.31
5.09
15
15.30
14.51
13.87
13.23
12.30
11.36
10.42
5.07
20
15.76
14.90
14.05
13.19
12.33
11.47
10.61
5.06
Power
consumption (kW)
VLT (°C)
30
35
40
45
50
55
60
65
TO (°C)
-25
2.32
2.60
2.89
3.17
3.43
3.69
3.63
--
-20
2.58
2.89
3.19
3.49
3.59
3.68
3.62
--
-15
2.85
3.17
3.50
3.82
3.75
3.67
3.61
--
-10
3.17
3.32
3.53
3.74
3.68
3.63
3.67
--
-7
3.35
3.41
3.55
3.69
3.68
3.60
3.71
--
-2
3.05
3.17
3.43
3.69
3.67
3.65
3.61
--
2
3.16
3.24
3.42
3.59
3.58
3.56
3.53
--
7
3.03
3.15
3.43
3.71
3.67
3.62
3.58
2.19
10
3.02
3.12
3.37
3.61
3.57
3.53
3.49
2.06
12
3.01
3.10
3.33
3.55
3.51
3.47
3.43
1.98
15
3.00
3.09
3.31
3.53
3.50
3.46
3.42
1.90
20
2.99
3.08
3.29
3.50
3.47
3.44
3.41
1.76
Coefficient of perfor-
mance (COP)
VLT (°C)
30
35
40
45
50
55
60
65
TO (°C)
-25
2.21
2.00
1.83
1.69
1.56
1.44
1.39
--
-20
2.41
2.18
1.99
1.79
1.74
1.65
1.54
--
-15
2.56
2.32
2.13
1.97
1.91
1.86
1.69
--
-10
2.74
2.55
2.34
2.17
2.07
1.97
1.82
--
-7
2.86
2.67
2.47
2.29
2.14
2.04
1.89
--
-2
3.49
3.24
2.96
2.72
2.56
2.41
2.16
--
2
3.78
3.54
3.24
2.97
2.82
2.67
2.38
--
7
4.62
4.20
3.74
3.35
3.08
2.81
2.53
2.32
10
4.84
4.44
3.98
3.57
3.33
3.07
2.81
2.46
12
5.00
4.61
4.14
3.74
3.50
3.25
3.00
2.57
15
5.10
4.69
4.19
3.75
3.52
3.28
3.04
2.67
20
5.27
4.84
4.27
3.77
3.55
3.33
3.11
2.88
▪
Heating capacity and power consumption at maximum heating capacity
▪
Heating capacity and power consumption at maximum compressor speed
▪
Power consumption without water pump
▪
Heating capacity and power consumption are measured according to EN 14511
TO: Outdoor temperature (TK°C)
VLT: Supply water temperature (°C)
HWT
-1101H(R)W-E NOMINAL HEA
TING CAP
ACITY
Содержание ESTIA R32 HWT-1101F21MT6W-E
Страница 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Страница 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Страница 8: ......
Страница 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Страница 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Страница 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Страница 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Страница 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Страница 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Страница 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Страница 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Страница 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Страница 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Страница 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Страница 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Страница 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Страница 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...