KNX module
IMPORTANT:
•
Only ever use one remote control. No additional remote controls can be used if you
connect this interface.
•
You cannot connect or mix Hydroboxes from series 4 and series 5.
Specification
Part
Specification value
Power supply unit
KNX line 29 VDC / 8 mA
AW line 14 VDC / 20 mA
Operating temperature and humidity
0°C to 40°C 10 to 80% RH (non-condensing)
Storage temperature and humidity
-20°C to 60°C 10 to 80% RH (non-condensing)
Casing material
Sheet metal box: galvanized sheet iron (SGCC-CSC) base 0.8 t; cover 0.6 t;
no coating; forming unit ABS (UL 94 HB) 2.5 mm thick
Size
Sheet metal box 33.4 (H) x 82.5 (W) x 92.1 (D) mm
Forming unit 28 (H) x 70 (W) x 70 (D) mm
Weight
225 g (including sheet metal box) 70 g (forming unit)
Supplied items
No .
Part designation
Quantity
Comments
1
KN interface (forming unit)
1
2
Operating instructions
1
3
Sheet metal box
1
Cover, base
4
Fastening screws
Use the following wiring material to connect the signal lines (to be procured on site)
No .
Cable
Part
Value
1
For KNX TP-1 bus
Cable type
KNX TP1
Cable diameter
Cable length
1000 m
Polarity
Yes (+/-)
2
For AB bus (AW-LINK) lines
Cable type
VCTF
Cable diameter
0.5 mm
2
to 2.0 mm
2
Cable length
50 m (0.75
2
)
Polarity
No
KN Interface
Installation Manual
2
-EN
Safety instructions
WARNING
Follow carefully these safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the interface
and/or the Hydro unit.
• This interface must be installed by accredited technical personnel (electrician, KNX installer, or technical personnel) and following all the safety instructions.
• This interface must only be installed in a restricted access location.
• Before manipulating the Hydro unit, be sure it is completely disconnected from Mains power.
• Do not modify the unit. (A fire or an electric shock may occur)
• This interface must only be installed in a restricted access location by user.
• Do not install the unit in any of the following places.
• Humid or wet place
• Dusty place
• Place exposed to direct sunlight
• Place where there is a TV set or radio within one meter
• Place exposed to rain (outdoors, under eaves, etc.)
• Use predefined cable and connect them certainly. Keep the connecting terminal free from external force.
It may cause an exothermic or a fire.
• Strip the insulation from the cable that connects to the connector (KNX and A B bus) following the dimensions shown in the diagram below.
• When connecting the cable to the connector (KNX and A B bus), ensure the core wires do not protrude from the connector.
• Use two-core cabtyre cable.
• Disconnect the KNX bus from power before manipulate it and connect it to the interface.
• To prevent EMC disturbances, ensure that there is a safety separation (SELV) of the connected signal cables (including possible extensions) from the other
voltage carrying devices and cables.
Installation instructions
• Disconnect the Hydro unit from Mains Power.
• Disconnect the power supply of the KNX bus.
• Connect the connection cable between the interface and the Hydro unit following the instructions of the diagram below.
• Connect the KNX bus to the connector KNX of the interface. Respect the polarity.
• Close the Hydro unit and reconnect it to Mains Power.
• Reconnect power supply to the KNX bus.
• Follow the instructions on the user's manual for configuring and commissioning the interface. See below how to obtain the user's manual and the ETS database.
IMPORTANT:
• Use only one remote controller. A sub-remote controller cannot be connected when connecting this interface.
• It is not possible to mix and connect Hydro unit 4 series and 5 series.
NOTE
The cable used for connection of BMS-IFKX0AWR-E to A B bus can be any two-core cabtyre cable, the maximum distance for bus A B is 50 meters, consult the
manual of the Hydro unit for more details.
NOTE
In its place there is a pair of cables to connect the Remote Controller. Use these cables to connect the AB bus. Check your Hydro unit user or service manual for
more information.
A
TB07
B
(20 mm)
(5 mm)
Hydro Unit
The terminal
block in the
hydro unit.
Connection to A B bus.
Two-core cabtyre cable.
Length of stripped KNX and A B bus communication
cable
Max. 50m
KNX TP-1
(EIB) bus
KNX MODULE
Содержание ESTIA R32 HWT-1101F21MT6W-E
Страница 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Страница 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Страница 8: ......
Страница 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Страница 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Страница 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Страница 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Страница 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Страница 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Страница 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Страница 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Страница 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Страница 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Страница 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Страница 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Страница 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Страница 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...