16 I
TOSHIBA
16 I
TOSHIBA
Storage location
Function code
no .
*HB= Hydrobox EEPROM
*RC= Remote Control
FC description
HB*
RC*
Range
Preset
Additional info
Settings:
automatic
curve for heating
Outdoor temperature T0 (°C)
A1
–
-20 (-30)~
-15 (-20)°C
-20
Zone 1:
Zone 1+2:
Zone 2:
Outdoor temperature T1 (°C)
29
–
-15~0°C
-10
Outdoor temperature T3 (°C)
2B
–
0~15°C
10
Setting of temperature A to T0 (°C) - ZONE 1
2C
–
20~55°C (65°C)
40
Setting of temperature B to T1 (°C) - ZONE 1
2D
–
20~55°C (65°C)
35
Setting of temperature C to T2 (°C) - ZONE 1
2E
–
20~55°C (65°C)
30
Setting of temperature D to T3 (°C) - ZONE 1
2F
–
20~55°C (65°C)
25
Setting of temperature E to 20°C (°C) -
ZONE 1
30
–
20~55°C
(65°C)
20
Ratio of Zone 2 to Zone 1 auto mode (%)
31
–
0~100%
80
ZONE 2
Temperature setting
0 = Percentage (DN 31)
1 = Set value (DN A3~A5)
A2
–
0~1
0
Setting of temperature A’ to T0 (°C) - ZONE 2
A3
–
20~55°C
(65°C)
40
Setting of temperature B’ to T1 (°C) - ZONE 2
A4
–
20~55°C
(65°C)
35
Setting of temperature E’ to 20°C (°C) -
ZONE 2
A5
–
20~55°C
(65°C)
20
Automatic curve - temperature change (°C)
27
–
-5~5°C
0
Frost protection
Frost protection
0 = Invalid
1 = Valid
3A
-
0-1
1
Frost protection ON/OFF
Frost protection target value (°C)
3B
-
10-20°C
15
Supply water temp. target value in frost protection
mode should be set to +20°C
Holiday function: Days
-
12
0-20
0
Number of days the mode remains in operation
Holiday function: Start time
-
13
0-23
0
Time of day at which the mode is ended
Backup heater control
Electric heating coil downward control
Heat pump 0 = 5 min.;
1 = 10 min.; 2 = 15 min.; 3 = 20 min.
33
-
0-3
1
Upward and downward control of the backup heater
stages based on the difference between the set
temperature defined on the remote control and
the supply water temperature downstream of the
backup heater (THO sensor)
Electric heating coil upward control
Heat pump 0 = 10 min.; 1 = 20 min.
2 = 30 min.; 3 = 40 min.
34
-
0-3
0
Set to 3 when using a buffer tank
0= No restriction
1= 20°C 3= 10°C 5=
0°C
2= 15°C 4= 5°C 6= -5°C
B8
-
0-6
0
Outdoor temperature from which the backup heater
is no longer switched on (measured at the TO
sensor)
0= 0K 2= 20K 4= 40K
1= 10K 3= 30K
B9
-
0-4
0
Temperature difference between TSC-F (target
heating value, e.g., Zone 1 +40°C) - THO
(Sensor downstream of backup heater, e.g.,
+10°C) = 30 K (if, e.g., B9 = 3 is set, the backup
heater would switch on at 3 kW at +10°C THO
temperature.)
Capacity of the backup heater
0 = 3 kW
1 = 6 kW
2 = 9 kW
6BC
-
0~2
Dependent on
type
Night setback (do not
use with FBH)
Night setback temperature
26
-
3-20°C
5
Kelvin by which the temperature is reduced
Zone selection 0= Zone 1&2; 1= Zone 1
58
-
C0~1
0
Zones in which the temperature is reduced
Start time
-
OE
0~23
22
Time at which the night setback begins
End time
-
OF
0~23
6
Time at which the night setback ends
Percentage method
Auto curve in ZONE 2 controls 80% (FC31) of Zone 1.
The water temperature setting does not drop below 20°C.
Set temperature in ZONE2 for A‘ °C at an outdoor tempera-
ture of T0°C, B‘ °C at T1°C, E‘ °C at 20°C
Fixed temperature method
FUNCTION CODES
Содержание ESTIA R32 HWT-1101F21MT6W-E
Страница 1: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...
Страница 3: ...8 11 14 16 h LI 1 Ph LI 1 Ph LI h LI 1 Ph LI 1 Ph LI 3 Ph 1 Ph 3 Ph 3 Ph h h 1 Ph 3 Ph 3 Ph ...
Страница 8: ......
Страница 26: ...26 I TOSHIBA 26 I TOSHIBA SCHEMA 1 0 ...
Страница 27: ...TOSHIBA I 27 TOSHIBA I 27 SCHEMA 1 1 ...
Страница 28: ...28 I TOSHIBA 28 I TOSHIBA SCHEMA 2 0 ...
Страница 29: ...TOSHIBA I 29 TOSHIBA I 29 SCHEMA 2 1 ...
Страница 30: ...30 I TOSHIBA 30 I TOSHIBA SCHEMA 3 0 ...
Страница 31: ...TOSHIBA I 31 TOSHIBA I 31 SCHEMA 3 1 ...
Страница 32: ...32 I TOSHIBA 32 I TOSHIBA SCHEMA 4 0 ...
Страница 33: ...TOSHIBA I 33 TOSHIBA I 33 SCHEMA 4 1 ...
Страница 34: ...34 I TOSHIBA 34 I TOSHIBA SCHEMA 5 0 ...
Страница 35: ...TOSHIBA I 35 TOSHIBA I 35 SCHEMA 6 0 ...
Страница 36: ...36 I TOSHIBA 36 I TOSHIBA SCHEMA 7 0 ...
Страница 37: ...TOSHIBA I 37 TOSHIBA I 37 WIRING DIAGRAM 230 V ...
Страница 38: ...38 I TOSHIBA 38 I TOSHIBA WIRING DIAGRAM 400V ...
Страница 41: ...APPENDIX R32 VERSION 1 0 Manual for ESTIA air to water heat pump ...