4.2.1. LAO Point Descriptions
Table 5
Logical Analog Output (LAO)
Point Descriptions
Point
Number
Point
Name
Description
01 CTLR
ADDRESS
The FLN address of the drive. It can be set from the FLN network and by
the panel. *1:
f834
02
APPLICATION
The Application ID for APG001Z.
20 OVRD
TIME
1 of the 5 mandatory FLN points required for compatibility with Siemens
control systems. It has no functionality in the drive application.
30
CURRENT LIM
Sets the output current limit of the drive. *1:
f601
31
ACCEL TIME 1
(Note1)
Sets the acceleration time for ramp 1. *1:
acc
32
DECEL TIME 1
(Note1)
Sets the deceleration time for ramp 1. *1:
dec
46
AO 1 COMMAND
Controls analog output 1(FM).
The FM analog terminal on each inverter can be directly controlled with the
computer. To use this function, set the FM terminal meter selection
parameter (
fmsl
) to 31 (communication data output).
This makes it possible to send out the data specified as FM analog output
data (AO 1 COMMAND) through the FM analog output terminal. Data can be
adjusted in a range of 0 to 2047 (resolution of 11 bits).
For details, refer to “Meter setting and adjustment” of the instruction manual
included with the inverter.
47
AO 2 COMMAND
Controls analog output 2(AM).
The AM analog terminal on each inverter can be directly controlled with the
computer. To use this function, set the AM terminal meter selection
parameter (
amsl
) to 31 (communication data output).
This makes it possible to send out the data specified as AM analog output
data (AO 2 COMMAND) through the AM analog output terminal. Data can be
adjusted in a range of 0 to 2047 (resolution of 11 bits).
For details, refer to “Meter setting and adjustment” of the instruction manual
included with the inverter.
50
PRC PID GAIN
Sets the proportional gain of the
PID. *1:
f362
51
PRC PID ITIM
Sets the integration time of the
PID. *1:
f363
52
PRC PID DTIM
Sets the derivation time of the
PID. *1:
f366
53
(PRC PID DFIL)
Reserved (does not work).
60 INPUT
REF1
Sets setpoint 1. This setpoint is enabled at #26 EXT1.2 CMD = 0.
For being available, some parameter(s) of the drive command require(s) a
specific configuration (setpoint channel 1).
61 INPUT
REF2
Sets setpoint 2. This setpoint is enabled at #26 EXT1.2 CMD = 1.
For being available, some parameter(s) of the drive command require(s) a
specific configuration (setpoint channel 2).
66
SPD OUT MIN
Sets the minimum output speed of the drive as a percentage of the motor
nominal rating. *1:
ll
67
SPD OUT MAX
Sets the maximum output speed of the drive as a percentage of the motor
nominal rating. *1:
ul
95
MBOX PARAM
Sets the parameter to be used by the mailbox function. Refer to section 5.
96
MBOX DATA
Sets or indicates the data value of the mailbox function. Refer to section 5.
99 ERROR
STATUS
1 of the 5 mandatory FLN points required for compatibility with Siemens
control systems. It has no functionality in the drive application.