E6581542
①
- 26 -
<
Example>
The example below shows how to configure the VF-PS1 for local/remote operation.
F terminal
.....................
Operating command
R terminal
....................
The APOGEE® FLN local/remote (Terminal in this example) switching
RR/S4 terminal
..........
Operation frequency command
<Wiring>
VF-PS1
F
R
CC
PP
RR/S4
Variable resistor for adjustment
10k ohm
The APOGEE® FLN
/local Switch
Operation command
SINK
SW1
SOURCE
CCA
<Parameter setting>
cmod
(Command mode selection) = 0 (Terminal board)
fmod
(Frequency setting mode selection 1) = 2 (RR/S4)
f112
(Input terminal selection 2 (R)) = 48 (Remote/Local control)
<Operation>
R-CC terminal open: VF-PS1 is controlled as a slave device of The APOGEE
®
FLN.
R-CC terminal closed:
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the RR/S4 signal input.
(Note)
When the local(HAND) / remote key (
f750
=
2
) is chosen as EASY key selection and
the EASY key lamp of an inverter front panel is on, priority is most given to operation by
a panel. (Refer to the inverter instruction manual for details).
Note that the HAND mode of the panel has priority over FLN local control.