10. Command & Setpoint selection (Local/Remote)
Indication to display Local/Remote mode is on the inverter unit (Refer to the inverter
instruction manual for details). APOGEE
®
FLN option command and setpoint are
activated on Remote mode.
Inverters have some switches to select the command and setpoint location. Following
figure shows the diagram. Refer to the inverter instruction manual for the parameter in
detail.
Command
Setpoint
Operation Panel
EASY key
(
f750
=
2
)
(Local/Remote key)
Logic input = 48 (SC/LC)
Network cancel switch
Network (APOGEE
®
FLN)
Network (APOGEE
®
FLN)
LDO point #68
*1
LDO point #69
*1
0
1
ON
OFF
0
1
Operation Panel
ON
OFF
Control Terminal (VI)
Control Terminal (RR)
:
Operation Panel
:
Network (APOGEE
®
FLN)
:
fmod
1
2
:
4
:
7
Control Terminal
Operation Panel
:
Network (APOGEE
®
FLN)
cmod
0
1
:
4
Remote
Loccal
Remote
Loccal
*1
Be careful that
cmod
command and
fmod
setpoint are activated for a short time
just after the inverter power turned on. Set
cmod
and
fmod
to “network” to
prevent this problem.