E6581542
①
- 13 -
4.3. Logical Digital Input (LDI) Summary
Logical Digital Input (LDI) points are used for drive status monitoring such as terminal
ON/OFF conditions and fault status. The APG001Z supports 24 different logical digital
input points. All LDI points support COV (LDI points are capable of being characterized).
LDI points will respond to write point and memorize point commands, but will not change
their actual values or indicate override active.
Table 6 Logical Digital Input (LDI) Summary
Point
Number
Point
Name
Factory
Default
Slope Intercept
ON (1)
Text
OFF (0)
Test
21 FWD.REV
FWD
1
0
REV
FWD
23 STOP.RUN
STOP
1
0
RUN
STOP
25
EXT1.2 ACT
EXT1
1 0 EXT2 EXT1
27 DRIVE
READY
NOTRDY
1
0
READY NOTRDY
28 AT
SETPOINT
NO
1
0
YES
NO
33 HANDAUTO
ACT
AUTO
1
0
HAND
AUTO
36
FLN LOC ACT
AUTO
1
0
FLN
AUTO
37 CTL
SRC
NO
1
0
YES
NO
38
FLN REF1 SRC
NO
1
0
YES
NO
39
FLN REF2 SRC
NO
1
0
YES
NO
70
DI 1 ACTUAL (F)
OFF
1
0
ON
OFF
71
DI 2 ACTUAL (R)
OFF
1
0
ON
OFF
72
(DI 3 ACTUAL)
OFF
1
0
ON OFF
73
DI 4 ACTUAL(RES)
OFF
1
0
ON OFF
74
DI 5 ACTUAL(S1)
OFF
1
0
ON OFF
75
DI 6 ACTUAL(S2)
OFF
1
0
ON OFF
76
DO 1 ACTUAL (FL)
OFF
1
0
ON
OFF
77
DO 2 ACTUAL (OUT1)
OFF
1
0
ON
OFF
78
DO 3 ACTUAL(OUT2)
OFF
1
0
ON OFF
79
DO 4 ACTUAL(R2)
OFF
1
0
ON OFF
80
DO 5 ACTUAL(OUT5)
OFF
1 0 ON OFF
81
DO 6 ACTUAL(OUT6)
OFF
1 0 ON OFF
86 OK.ALARM
OK
1
0
ALARM
OK
93 OK.FAULT
OK
1
0
FAULT
OK