4.4. Logical Digital Output (LDO) Summary
Logical Digital Output (LDO) points are used for executing drive commands such as
RUN/STOP and trip clear. The APG001Z supports 18 different logical digital output points
(17 among them are for drive control, one special point is reserved for maintaining
compliance). The values of all logical digital output points can be modified by write point
or memorize point commands. Release commands will not cause the logical digital output
points to automatically return to their pre-override values. LDO points do not support
COV.
Table 8 Logical Digital Output (LDO) Summary
Point
Number
Point
Name
Factory
Default
Slope Intercept
ON (1)
Text
OFF (0)
Test
22 CMD
FWD.REV
FWD
1
0
REV
FWD
24 CMD
STP.STRT
STOP
1
0
RUN
STOP
26 EXT1.2
CMD
EXT1
1
0
EXT2
EXT1
29 DAY.NIGHT
DAY
1
0
NIGHT
DAY
40
DO 1 COMMAND (OUT1) *
OFF
1
0
ON
OFF
41
DO 2 COMMAND (OUT2) *
OFF
1
0
ON
OFF
42
DO 3 COMMAND (FL) *
OFF
1
0
ON
OFF
43
DO 4 COMMAND (OUT3) *
OFF
1
0
ON
OFF
44
DO 5 COMMAND (OUT4) *
OFF
1
0
ON
OFF
45
DO 6 COMMAND (R1) *
OFF
1
0
ON
OFF
48
(RST RUN TIME)
NO
1
0
RESET
NO
49 RESET
KWH
NO
1
0
RESET
NO
59 LOCK
PANEL
UNLOCK
1
0
LOCK UNLOCK
68
FLN LOC CTL
AUTO
1
0
FLN
AUTO
69
FLN LOC REF
AUTO
1
0
FLN
AUTO
94 RESET
FAULT
NO
1
0
RESET
NO
97 MBOX
READ
DONE
1
0
READ
DONE
98 MBOX
WRITE
DONE
1
0
WRITE
DONE
*
Example
:
Set the parameter
f130
(
OUT1
terminal) = 92 (93).
Set the parameter
f131
(
OUT2
terminal) = 94 (95).
Set the parameter
f132
(
FL
terminal) = 96 (97).
Set the parameter
f133
(
OUT3
terminal) = 98 (99).
Set the parameter
f134
(
OUT4
terminal) = 100 (101).
Set the parameter
f135
(R1 terminal) = 102 (103).