172-65702M-04 (SQ-C01) 10 Dec 2020
10
Component Configuration
Name
No. Component
Description
Steam Supply
Unit
①
Pressure reducing
valve for steam
Adjusts the steam pressure supplied to
the unit.
・
Fine adjustment of the steam pressure
is possible with the built-in pressure
reducing valve.
Heat Exchanger
Unit
②
Heat Exchanger
Produces hot water by exchanging
heat from steam supplied by the steam
supply unit (heating side) to water
(heated side).
⑨
Pressure gauge for
steam
Water Inlet
Piping Unit
⑥
Line relief valve
(Water Safety Valve)
Channels supplied cold water to each unit.
・
Cold water is channelled to three
locations: heat exchanger unit,
pre-mixing unit, and mixing unit.
・
The line relief valve (water safety valve)
prevents the internal pressure of the
equipment from exceeding a certain level.
⑦
Heat insulating joint
Pre-mixing Unit
③
Pre-mixing Valve
The hot water produced in the heat
exchanger unit is mixed with cold
water to prevent the water from
exceeding a certain temperature.
・
The pre-mixing valve is one of the
safety features that prevents abnormally
high temperature water from being
discharged.
⑦
Heat insulating joint
Mixing Unit
④
Mixing Valve
Produces hot water of the required
temperature by mixing hot water and
cold water that have passed through
the pre-mixing unit.
・
The temperature of the mixing valve can
be adjusted by turning the temperature
adjustment dial.
⑦
Heat insulating joint
Hot Water
Outlet Unit
⑧
Thermometer
Displays the water temperature
produced in the mixing unit and
supplied.
・
Temperature can be adjusted while
checking the thermometer.
・
The shock absorber absorbs a certain
amount of shock generated inside and
around the water piping inside the
equipment to prevent damage to the
equipment.
⑤
Shock absorber
Standard accessories
(delivered separately)
Name
No.
Description
Steam Trap
⑩
Installed on the condensate outlet piping to discharge the
condensate in the heat exchanger unit.
・
J3X-8 (Rc ½) and TLV strainer
Strainer
(for cold water
inlet)
⑪
Removes dust and scale from the supplied cold water.
Make sure to install the strainer correctly.
・
TLV strainer (Rc ½), certified as conforming to the Water Supply
Act (Japan).
Note: - The gaskets and bolts included are intended for use with standard accessories only