Pag. 19
Tot 27.
THERMOSALD UPSCR_M_V3
08/2000
6 LIST OF WARNING AND FAULT MESSAGES ( CAUSES - REMEDIES )
Display
CAUSES
REMEDIES
F081
check-sum fault
Press RESET / MODE
Shut-down while data being updated
Contact the manufacturer.
Hardware problem
F082
Fault - control circuit supply (CN2) and
Make changes to the electrical system as shown in
power circuit supply (CN1) not synchronised
the wiring diagram.
F083
Fault - signal leads wrong way round
Reverse the signal leads
( CN3/6 - CN3/7 )
F084
Fault - power transformer voltage
Check transformer rating ( Chap 4.1 )
too high
Check dip switches SW+ SW-
F085
Fault - sealing time higher than machine
Enter new maximum time and check the
set data 7.XXX .
electronic timer
F086
Fault - mains voltage decreased by
Check mains voltage. The fault message is displayed until the RESET
more than 10 %.
key is pressed. The card still works but a few cold sealing operations may
be performed due to the voltage drop.
F087
Fault - mains voltage decreased by
Check mains voltage. The fault message is displayed until the RESET
more than 10 % during sealing
key is pressed. The card still works but a few cold sealing operations may
be performed due to the voltage drop.
F089
Fault - band broken if the bands are
Check bands
parallel-connected
F090
Fault - short circuit
Check the machine for shorts
between the bands or between the bands
and earth connection
F091
Fault I2T
Check for abnormal absorption
F092
Fault - power part malfunctioning
Hardware problem , contact the manufacturer
F093
Fault - band broken if the bands
Replace the band and/or sealing wire
are series-connected
Check that power is supplied when the sealing signal is given
F094
Fault- signal lead is pinched
Check signal lead connections
( CN3/6 - CN3/7 )
F095
Fault - mains supply does not match
Hardware problem , contact the manufacturer
machine requirements
F096
Fault V-I Wrong setup
Check SW1
Check BALANCING trimmer
F097
Fault - partial short-circuit between the bands
Check sealing jaws
or between the bands and earth connections
F098
No current delivered during calibration
Check power supply
F099
Eeprom fault
Contact supplier
NOTE - Press the RESET / MODE key to clear the fault message.
.