The machine data can be used to adapt the temperature controller for a specific application.
Press the RESET/MODE and DOWN keys for 6 seconds ( 0.0.0.0. will appear on the display).
•
0.0.0.0. INITIAL MACHINE DATA
•
Press the RESET/MODE key.
•
1.XXX HEATING INCREASE (The temperature increase following a pre-heat or sealing signal is shown on the
display in degrees/10 ms). To change the value use the UP and DOWN keys.
Decrease the value of this parameter to increase the time required to bring the band up to the correct temperature and,
as a result, increase the amount of time the band lasts.
•
Press the RESET/MODE key.
•
2.XXX KV GAIN ( the value of the proportional closed-loop gain appears on the display): to change this value, use
the UP and DOWN keys.
Increase the value of this parameter to increase the closed-loop response speed and make the system quicker to come
into action.
An excessive KV increase may cause input currents to become unsteady and therefore lead to temperature fluctuation.
•
Press the RESET/MODE key.
•
3.XXX KINT GAIN ( the integral closed-loop gain value appears on the display ): to change the value, press the UP
and DOWN keys.
To increase system stability, increase this parameter.
An excessive KINT increase may lead to an overtemperature after a pre-heat signal ( this parameter is not active during
the sealing operations).
•
Press the RESET/MODE key.
•
4.XXX KINT OPERATING LIMIT ( This limit appears on the display ): to change the value, press the UP and
DOWN keys.
This parameter should not be changed.
•
Press the RESET/MODE key.
•
5.XXX SELECT °C / °F DISPLAY ( the value selected is shown on the display as 00C / 00F ): to change the value,
press the UP and DOWN keys.
•
Press the RESET/MODE key.
•
6.XXX SELECT MAINS FREQUENCY 50 / 60 Hz ( the value is shown on the display as 050 / 060 ): to change
the value, press the UP and DOWN keys.
•
Press the RESET/MODE key.
•
7.XXX MAXIMUM SEALING TIME ( the maximum sealing time expressed in seconds appears on the display).
To change the value, press the UP and DOWN keys.
This function is used to control the maximum sealing time. If the actual sealing time is longer than this value, the
controller sends fault signal F085.
For applications where the sealing signal is kept high, this parameter should be set to 000. In this case parameter 3
(KINT gain) is enabled even during sealing.
•
Press the RESET/MODE key.