Pag. 11
Tot 27.
THERMOSALD UPSCR_M_V3
08/2000
(this operation allows the user to check the machine during the first start-up procedure. Set dip switches SW1, set the
IREAD dip switches, set the heating factor. This allows the user to check the state of the machine whenever
maintenance problems arise)
AUTOMATIC CALIBRATION
In "hot calibration" mode, deliver a SET CURRENT so that the band reaches a temperature of 100°C (212°F)
•
Press the RESET/MODE and UP keys for 6 seconds ( 1.1.1.1. appears on the display)
••••
Press the RESET/MODE key.
•
0.XXX SET CURRENT ( the set current expressed in A appears on the display) : set the current by pressing the UP
and DOWN keys and wait for the machine to heat up until the band reaches a temperature of 100°C/212°F (check with
a thermometer)
••••
Press the RESET/MODE key.
••••
1.XXX HEATING FACTOR V-I (a reference value which should be between 0.8 and 1.6 will appear on the display).
To check this value, the machine should be at 100°C/212° F. To change this value, change the setting for dip switches
SW1
Dip 1
Dip 2 Dip 3 Dip 4
(binary system)
Minimum value
ON
ON
ON
ON
Most recurrent value OFF
ON
ON
ON
Higher value
ON
OFF
ON
ON
(for this setting or higher settings,
Higher value
OFF
OFF
ON
ON
contact our engineering dept.)
"
Maximum value
OFF
OFF
OFF
OFF
(do not use)
•
Press the RESET/MODE key.
•
2.XXX CALIBRATION I READ (a reference value which should be between 3.0 and 3.8 will appear on the display).
To check this value, the machine should be at 100°C/212° F. To change this value, change the setting for dip switches
SW1
Dip 1
Dip 2 Dip 3 Dip 4
(binary system)
Minimum value
ON
ON
ON
ON
Higher value
OFF
ON
ON
ON
Higher value
ON
OFF
ON
ON
Higher value
OFF
OFF
ON
ON
Higher value
ON
ON
OFF
ON
"
Maximum value
OFF
OFF
OFF
OFF
•
Press the RESET/MODE key.
•
3.AAA HEATING FACTOR ACQUISITION ( 3.A.A.A. should flash on the display ): under this condition, the
temperature controller automatically acquires heating factor 5.XXX
•
Press the RESET/MODE key.
•
4.XXX PEAK CURRENT ( the peak current expressed in A appears on the display )
•
Press the RESET/MODE key.
•
5.XXX HEATING FACTOR V-I ( the V-I heating factor appears on the display. To change the factor, use the UP
and DOWN keys to increase or decrease the machine temperature)
•
To quit, press the RESET/MODE key for 3 seconds.