Specifications (Rev. 04/03)
2
R-404A REFRIGERATION SYSTEM
Compressor Model
X214
Refrigerant Charge
7.5 lb. (3.4 kg) R-404A
Compressor Oil Charge
66 oz. (1.95 liters)*
Compressor Oil Type: R-404A (Solest 35)
TK No. 203-413 (Ester base) required
Suction Pressure Regulator Setting
Special Setting KD-II Single Phase
18 psig (124 kPa)
18 psig (124 kPa)
Heat/Defrost Method: Engine Operation
Electric Operation
Hot gas
Hot gas and electric heater strips (Model 50)
High Pressure Cutout
470 ± 7 psig (3241 ± 48 kPa)
Automatically reset @ 375 ± 38 psig
(2585 ± 262 kPa)
NOTE: Compressors are equipped with an oil filter. Every 2 years of operation or whenever there is a
major service procedure performed, both the compressor oil filter and filter-drier must be changed.
* When the compressor is removed from the unit, oil level should be noted or the oil removed from the
compressor should be measured so that the same amount of oil can be added before placing the
replacement compressor in the unit.
HIGH PRESSURE RELIEF VALVE
Opens
500 ± 50 psig (3448 ± 345 kPa)
Closes
400 psig (2758 kPa)
ENGINE CLUTCH—HILLIARD (Prior April 1997)
Model
TK No. 107-257 (Dwg. No. 5D44655G01)
Engagement
900 ± 100 rpm
Dynamic Torque
66 ft-lb (89.5 N•m) minimum @ 1600 rpm
ENGINE CLUTCH—HILLIARD (Starting April 1997)
Model
TK No. 107-272 (Dwg. No. 2C21375G01)
Engagement
600 ± 100 rpm
Dynamic Torque
66 ft-lb (89.5 N•m) minimum @ 1600 rpm
BELT TENSION
Tension No. on TK Gauge 204-427
New Belt
Field Reset
Engine/Compressor
75 ± 3
70 ± 3
Compressor/Motor Drive (Jackshaft)
72 ± 3
67 ± 3
Compressor/Evaporator Fan/Alternator
55 ± 3
50 ± 3
Alternator/Evaporator Fan
55 ± 3
50 ± 3
Water Pump
1/2 in. (13 mm) deflection
NOTE: These are the original factory settings. Because it is difficult to use the TK gauge 204-427 in the
field, adjust each belt to allow 1/2 inch (13 mm) deflection at the center of the longest span.
NOTE: Belts should be tensioned cold and again tensioned cold after 10 hours of unit running.
Содержание KD-II SR
Страница 4: ......
Страница 8: ......
Страница 13: ...Safety Precautions Rev 04 03 v AEA40...
Страница 14: ...Safety Precautions Rev 04 03 vi AEA38...
Страница 33: ...Unit Description Rev 04 03 19 1 Evaporator 2 Access Door Rear View Curbside KD II SR 1 2 AEA38...
Страница 37: ...Unit Description Rev 04 03 23 Power Receptacle Box KD II SR 50 AEA42...
Страница 38: ...Unit Description Rev 04 03 24 1 Keypad 2 LED Display THERMOGUARD Remote Control Panel AEA43 1 2...
Страница 42: ...P T System Description Rev 04 03 28 High Voltage Tray No Options High Voltage Tray with Phase Correction...
Страница 44: ...P T System Description Rev 04 03 30 High Voltage Tray with Single Phase Power and Electric Heater...
Страница 58: ...Remote Control Panel Features Rev 04 03 44...
Страница 112: ...Refrigeration Maintenance Rev 04 03 98...
Страница 120: ...106...
Страница 146: ...132...
Страница 156: ...142...
Страница 162: ...148...
Страница 170: ...156...
Страница 172: ...158...
Страница 173: ...159 KD II 30 Schematic Diagram Page 1 of 2...
Страница 174: ...160 KD II 30 Schematic Diagram Page 2 of 2...
Страница 175: ...161 KD II 30 Wiring Diagram Page 1 of 2...
Страница 176: ...162 KD II 30 Wiring Diagram Page 2 of 2...
Страница 177: ...163 KD II 50 Schematic Diagram Page 1 of 2...
Страница 178: ...164 KD II 50 Schematic Diagram Page 2 of 2...
Страница 179: ...165 KD II 50 Wiring Diagram Page 1 of 2...
Страница 180: ...166 KD II 50 Wiring Diagram Page 2 of 2...
Страница 181: ...167 KD II 50 SR 230 1 60 Wiring Diagram Page 1 of 2...
Страница 182: ...168 KD II 50 SR 230 1 60 Wiring Diagram Page 2 of 2...