background image

To determine how each control operates the UA-90H, it must 
first be determined which control is being used and whether 
or not the 90H is ducted for fresh air ventilation. Refer to 
appropriate section. 

Humidity/Fan Control Panel (P/N 4024155) (Figure 1, p.7) 

4.6A   

  Humidity/Fan Control Panel WITHOUT Fresh Air   
Ventilation or Damper  

4.6B   

 Humidity/Fan Control Panel WITH Fresh Air   
Ventilation and WITHOUT Damper  

4.6C   

 Humidity/Fan Control Panel WITH Fresh Air  
Ventilation AND Damper  

Ventilation Timer/Humidity Control Panel (P/N 4024125)  
(Figure 2, p.7) 

4.6D  

 Ventilation Timer and Humidity Control WITH Fresh Air 
AND Motorized Damper 

DEH 3000 Digital Control (P/N 

4026570

)

4.6E  

Digital Controller WITH Fresh Air AND Damper 

4.6F  

Digital Controller WITHOUT Fresh Air 

4.6A Humidity/Fan Control Panel WITHOUT Fresh Air 

Ventilation or Damper 

The humidity/fan control panel automatically controls the humidity 
of the living space. The humidity/fan control panel contains an 
adjustable humidity control and a fan switch. The panel has a 
cover that must remain open to the air within the living space for 
accurate humidity sensing. When the fan switch is in the “ON” 
position, air will be continually filtered and circulated throughout 
the home. For humidity control operation refer to section 4.7. 

4.6B Humidity/Fan Control Panel WITH Fresh Air 

Ventilation and WITHOUT Damper 

The humidity/fan control panel automatically controls the humidity 
of the living space. The humidity/fan control panel contains an 
adjustable humidity control and a fan switch. The panel has a 
cover that must remain open to the air within the living space for 
accurate humidity sensing. Outside air is continually introduced 
whenever fan is “ON.” Manual operation of fan filter switch controls 
outside air ventilation. Since the fan operates whenever the UA-90H 
is dehumidifying outside air will also be introduced. For humidity 
control operation refer to section 4.7. 

4.6C Humidity/Fan Control Panel WITH Fresh Air 

Ventilation AND Damper 

In this configuration, a motorized damper has been installed 
in the fresh air duct. When the fan/filter switch is in the “OFF” 
position, the damper is closed. The UA-90H will then circulate and 
dehumidify air to provide humidity control. 

When the fan/filter switch is in the “ON” position, the motorized 
damper will open and the fan will run, introducing outside air. The 
unit may or may not be dehumidifying in the ventilation mode, 
depending on the humidity control setting. See Section 4.7 for 
humidity control operation. 

4.6D Ventilation Timer and Humidity Control WITH 

Fresh Air AND Motorized Damper 

Refer to sections 4.7 through 4.9C. 

4.6E DEH 3000 Digital Control WITH Fresh Air AND 

Damper 

Refer to Section 5. 

4.6F DEH 3000 Digital Control WITHOUT Fresh Air 

Refer to Section 5. 

4.7 Humidity Control Adjustment 

Set the humidity control to the desired 
humidity level for the home. Turning the knob 
clockwise results in a drier setting. See the 
back of the control panel cover for set points. 
The dehumidifier will run continuously until 
the relative humidity (RH) is reduced to the 
humidity control dial setting. Setting the 
humidity control to lower RH levels will NOT 
increase the dehumidification rate; the unit will 

simply run longer to reduce the RH to the setting. The UA-90H unit 
(and refrigerant-based dehumidifiers in general) will reduce a warm 
space’s RH to a lower level than that of a cool space. Therefore 
there is no benefit to set the humidity control to excessively 
low levels in cool rooms; doing so will result in long periods of 
ineffective dehumidifier run time. Settings below 45% are not 
recommended. 

4.8 Fan/Filter Switch 

Turning ON the fan/filter switch will cause the 
UA-90H fan to run continuously, whether the 
UA-90H is dehumidifying or not. This function 
is desirable if the unit is used for air circulation 
and filtration to achieve maximum indoor air 
quality. When the switch is ON; air will be 
constantly filtered through the UA-90H and 
circulated throughout the house. When the 

switch is OFF the fan will operate only when the humidity control 
calls for dehumidification or when the ventilation timer calls for 
ventilation. 

FOR HVAC INSTALLER AND HOMEOWNER

Figure 3

Humidity Control 

Adjustment Knob

Figure 4

Fan/Filter Switch

8

Ultra-Aire 90H Installer’s & Owner’s Manual

9

Ultra-Aire 90H Installer’s & Owner’s Manual

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: