FOR HVAC INSTALLER ONLY

WARNING:

 

TO AVOID TRANSFORMER DAMAGE ONLY 

CONNECT THE WHITE WIRE TO THE CONTROL IF A DAMPER IS 
USED.

The white wire controls the optional motorized damper that 
can be installed into a fresh air duct. This provides the ability 
to control when fresh air is introduced into the building by 
using the ventilation timer function labeled “DMP” on the 
control (See Section 3.7). 

IF THE MOTORIZED DAMPER IS 

NOT USED,

 

DO NOT CONNECT THE WHITE WIRE TO THE 

CONTROL OR DAMAGE TO THE TRANSFORMER MAY 
RESULT.

 Simply leave the (DMP) terminal unused if the 

damper is not used, and cap off the white lead from the Ultra-
Aire dehumidifier.

2.3 Auxiliary relay operation

At times it may be desirable to coordinate fan operation 
of the central heating/cooling system with dehumidifier 
operation. The DEH 3000 features a relay that provides 
this ability. The relay terminals labeled NC, COM and NO 
operate according to the following chart:

  Dehumidification  
 

Operation 

COM/NO 

COM/NC 

 

ON 

CLOSED 

OPEN

 

OFF 

OPEN 

CLOSED 

Common uses (assuming standard thermostat wiring color 
schemes as noted):

Disengage A/C during dehumidification

Redirect the yellow thermostat wire to the NC terminal. Wire 
the yellow wire from the A/C to the COM terminal.

Engage the A/C central fan during dehumidification

1.  Disconnect the green wire that runs to the fan relay from the 

screw on the thermostat.

2.  Connect the green wire that runs to the fan relay to the COM 

screw on the DEH3000 board.

3.  Run a wire from the red wire screw on the thermostat to the NO 

(Normally Open) screw on the DEH3000 board.

4.  Run a wire from the green wire screw on the thermostat to the 

NC (Normally Closed) screw on the DEH3000 board.

The central fan should run when the Thermostat fan switch 
is turned to ON and when the dehumidifier is operating.

2.4 Dehumidifier lockout/activation:  
AC sensor feature

The control has the ability to activate the dehumidifier or 
deactivate the dehumidifier when the air conditioner is running.

Standard wire colors for thermostats are as follows:
Description 

Color 

Terminal code

24VAC Return 

Red 

R

Call for Heat 

White 

W or W1

Force Fan On 

Green 

G

Compressor 
Call for Cooling 

Yellow 

Y or Y1

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: