FOR HVAC INSTALLER ONLY AND HOMEOWNER

Operation

 

The initial dead band setting (the range that the dehumidifier 
cycles on and off) is 3%. With a setpoint of 50%, the dumidifier 
turns on when the reading reaches 53%. The dehumidifier 
continues to remove water from the air until the reading is 
47%. The dehumidifier remains off until the reading is 53%.

If the setpoint is equal to or greater than the current ambient 
condition, the space does not need to be dried so the 
dehumidifier function will be off.

Example: Setpoint: 50% RH 
Current condition: 45% RH = Dehumidifier off, the 

O

 

indicator will not be shown.

If the setpoint is less than the ambient condition, the 
dehumidifier will be on and the red “DEHU” indicator will be 
lit.  Since the space is more humid than the set point, the 
controller operates the dehumidifier to dry the space.

Example: Setpoint: 50% RH 
Current condition: 55% RH = Dehumidifier on, the 

O

  

indicator will be shown.

To set the relative humidity setpoint, press up or down 

“RH”

 

buttons to adjust the relative humidity setpoint as desired. 
Therma-Stor recommends relative humidity levels not exceed 
50% in the summer, and 25-35% in the winter if you live 
in a cold climate. It is not recommended that the humidity 
setpoint be set below 35%. In order to dry the home in the 
winter in a cold climate, use the ventilation function of the 
system rather than the dehumidifier function. Call the factory 
or refer to the owner’s manual for more information.

5.3F Fan Setting and Operation

Use the 

“FAN”

 button to adjust the fan operation. There are 

2 choices for fan operation: 

“ON”

 or 

“AUTO.”

  

“ON”

 – indicates the fan of the Ultra-Aire will run 

continuously.  This does not affect either the dehumidification 
or ventilation functions of the system.  In other words, the 
system may or may not be ventilating or dehumidifying while 
the fan is running. Common reasons for operating the fan 

continuously are filtration and air recirculation.

“AUTO”

 – indicates the fan will run when the control calls for 

dehumidification or ventilation. If the control has not called for 
dehumidification for 3 hours, the control will automatically run 
the fan for 10 minutes. The fan must run a specific amount of 
time per day. This helps to keep the dehumidifier dry.

After dehumidification cycle, fan automatically shuts off for 10 
minutes.`

To set the operation:

1.   Press and hold the 

“FAN”

 button. The current fan setting 

will begin to flash. Release the button.

2.   Press the 

“FAN”

 button to toggle between the 

“ON”

 and  

“AUTO”

 modes.

An 

O

 indicator indicates the fan is operating.  A flashing 

O

 indicator indicates the fan is in a wait mode and will 

operate shortly.  No 

O

 indicates the fan is off.

With the fan in the 

“AUTO”

 mode, the fan will operate only 

when needed by other functions of the system. The fan 
will remain off unless the system is dehumidifying and/or 
ventilating. The fan always runs during dehumidification and 
ventilation and the fan 

O

 icon will be lit. To completely turn 

the system off, use the 

“ON/OFF”

 button as described earlier. 

To adjust the ventilation mode see Section 3.7.  

5.3G Damper Operation and Setting (Ventilation) 
Manual/Hold Mode

Ultra-Aire units can be installed to incorporate optional ventilation. 
The damper setting controls the ventilation function of the system. 
It has no control over the dehumidification function, although 
the ventilation function can and should be used to dry the space 
depending on the climate and the outside air conditions. Refer to 
the appropriate Ultra-Aire manual for more information.

In order to provide ventilation, the damper must be open (

“ON”

and the fan must be running. The controller takes care of these 
two functions automatically, so that whenever the damper is open 
(

“ON”

), the fan is running. 

14

Ultra-Aire 90H Installer’s & Owner’s Manual

15

Ultra-Aire 90H Installer’s & Owner’s Manual

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: