1. 

 

Intended Application for Ultra-Aire 90H 

For the ideal installation, draw air from the central part of the home 
and return it to isolated areas of the home like the bedrooms, den, 
utility room, or family room. The ductwork of the existing heating 
system can be used to supply air to the home. 

2. Registrations 

The UA-90H conforms to UL STD 474 and CSA Standard C22.2 
No.92. 

3. Specifications 

Model:   

Ultra-Aire 90H  

Electrical:   

 110-120 VAC, 6.3 Amps, 60 Hz, grounded  

Capacity:   

90 pints/day @ 80°F, 60% RH  

Operating Temp.:   

56°F min., 100°F max.  

Air Flow:   

 200 CFM without external ducting  

Refrigerant Charge:   1 lb., 12 oz. R22
Duct Connections:  

Round 10" inlet, 10" outlet,

6" ventilation inlet Filter Size:  

Pleated cloth: 14" X 14" X 1" 

Unit Size (w/o duct collars):  

34

1

/

2

"L x 15

3

/

4

"W x 20

7

/

8

"H Unit 

Weight:  

92 lbs Shipping Weight: 99 lbs 

4. Installation 

4.1 Installation Checklist 

IMPORTANT

 

Prior to installation of the UA-90H, the following checklist should 
be reviewed. The UA-90H can be installed in a variety of locations 
to meet the owner’s needs, and integrate with existing forced 
air systems or existing ductwork if desired. The location choice 
is contingent on a variety of requirements not limited to: ease 
of service, controls access, drainage, filtration, power, fresh-air 
ventilation, water damage prevention, and current regulatory codes 
(ASHRAE, fire, etc). Please address all of these issues before you 
select the device’s location. 

n

  

4.1A Power Accessibility 

Unit should be located in an area where the cord’s  length (10’) 
should easily reach a 115 VAC electrical  outlet with a minimum of 
a 15 A circuit capacity. 

n

  

4.1B Space 

Location should have enough clearance to handle the unit’s overall 
dimensions as well as the necessary return/supply ductwork to the 
unit. 

n

  

4.1C Low Voltage Wiring 

Unit location should be in an area where field wiring the remote 
controls (low voltage) to the unit will be possible. 

n

  

4.1D Back-Draft Damper 

It is recommended that a back draft damper be used in the 
discharge duct of the UA-90H, especially when connecting to the 
supply ducting system. The backdraft damper prevents supply air 
from counter flowing through the UA-90H when it is not operating. 
The unit location should be chosen to allow installation of this 
accessory if requested by the end user. 

n

  

4.1E Support Structure and Suspension 

Place the UA-90H on supports to raise the base of the unit. Do not 
place the UA-90H directly on structural building members without 
vibration absorbers or unwanted noise may result. 

The UA-90H may be suspended with steel hanger straps (plumbers 
tape) or a suitable alternative from structural members, as long 
as the suspending assembly supports the UA-90H’s base in its 
entirety. Do not hang the UA-90H from the cabinet. Remember to 
place a drain pan under the unit if it is suspended above a finished 
area or above an area where water leakage could cause damage. 

4.2 Electrical Requirements 

WARNING 

WARNING: DO NOT ALLOW THE YELLOW LEAD FROM 

THE ULTRA-AIRE TO CONTACT THE RED LEAD FROM THE 

ULTRA-AIRE OR DAMAGE TO THE TRANSFORMER WILL 

RESULT. 

The UA-90H plugs into a common grounded 115VAC outlet. The 
device draws 6.3 Amps under normal operating conditions. If used 
in an area which may become wet, a ground fault interrupter (GFI) 
protected circuit is recommended. Please, consult local electrical 
codes for any further information. 

Therma-Stor LLC offers a family of control devices for use with the 
UA-90H. The controls are to be located remotely from the unit and 
located in the space to be conditioned. The controls are low voltage 
(24 volt) and should be connected to the UA-90H with low voltage 
wire (thermostat or other appropriate). 

FOR HVAC INSTALLER ONLY

4

Ultra-Aire 90H Installer’s & Owner’s Manual

5

Ultra-Aire 90H Installer’s & Owner’s Manual

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: