Unit not providing ventilation. Ventilation timer not operating 
correctly. 

1. If timer is not functioning correctly reset timer and reprogram. 
2. Check control wire connections (check connections at fresh 
air damper also). 
3. Defective fresh air damper. 
4.Defective fan switch. 

Unit removes some water, but not as much as expected. 

1. Air temperature and/or humidity have dropped. 
2.  Humidity meter and or thermometer used are  

out of calibration.

3. Unit has entered defrost cycle. 
4. Air filter dirty. 
5. Defective defrost thermostat. 
6. Low refrigerant charge. 
7. Air leak such as loose cover or ducting leaks. 
8. Defective compressor. 
9. Restrictive ducting. 
10.Optional Condensate Pump Safety Switch open. 

Unit Test to determine problem: 

1. Detach field control wiring connections from main unit. 
2.  Connect the yellow and green pigtails from the main unit 

together; only the fan should run. Disconnect the wires. 

3.  Connect the yellow and blue pigtails from the main unit 

together; the compressor and fan should run. 

4.  If these tests work, the main unit is working properly. You 

should check the control panel and field control wiring for 
problems next. 

5.  Remove the control panel from the mounting box and detach 

it from the field installed control wiring. Connect the blue, 
yellow, and green wires from the control panel directly to the 
corresponding colored pigtails on the main unit. Leave the 
violet, white and red wires disconnected! 

6.  Turn on the fan switch; the fan should run. Turn off the fan 

switch. 

7.  Turn on the humidity control; the compressor and fan should 

run. 

8.  If these tests work, the problem is most likely in the field 

control wiring. 

11.3 Refrigerant Charging 

If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 
left in the system, it must be recovered before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type. 

11.4 Compressor/Capacitor Replacement 

This compressor is equipped with a two terminal external overload 
and a run capacitor, but no start capacitor or relay. 

CAUTION

 

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power must 
be present to perform some tests. These tests should be 
performed by a qualified service person. 

11.5 Electric Ventilation Damper 

The electric ventilation damper is controlled by the ventilation timer. 
The damper will open when the ventilation timer is activated to 
allow fresh air into the structure through the 6" diameter fresh air 
inlet duct. The electric ventilation damper will remain closed when 
the ventilation timer is not activated to prevent over-ventilating 
the structure when the unit is dehumidifying or recirculating the 
indoor air. The electric ventilation timer operates on 24 Vac from the 
control circuit. DO NOT connect high voltage to the damper motor 
or damage to the motor may result. DO NOT force the blade of the 
damper by hand or damage to the damper motor may result. 

The damper opens in one direction only. The damper rotates very 
slowly, allow sufficient time for the damper to cycle. The damper 
will take approximately one minute to cycle from closed to open or 
from open to closed. 

If the electric ventilation damper fails to operate: 

1.  Check that the wiring is correct and that voltage is present at 

the damper motor. 

2.  Check for any obstruction inside the damper. If the electric 

ventilation damper fails to operate after performing these 
checks, it must be replaced. 

11.6 Condensate Pump Kit 

An optional condensate pump kit is available from the factory for 
use with the UA-90H. Condensate is automatically pumped to a 
remote location when the water level in the pump’s reservoir rises 
to close the float switch. The pump also contains a safety float 
switch. The white leads from this switch extend from beneath the 
pump cover. This switch should be installed in series with the field 
wire that connects the blue (#5) lead from the UA-90H to the blue 
(#5) lead on the control panel. If the pump fails, this switch opens 
the compressor control circuit and stops water production before 
the reservoir overflows. The UA-90H will continue to ventilate or 
circulate air as normal, but will not dehumidify until this switch 
closes.  See following pages for more information.

FOR HVAC INSTALLER ONLY

22

Ultra-Aire 90H Installer’s & Owner’s Manual

23

Ultra-Aire 90H Installer’s & Owner’s Manual

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: