IMPORTANT 

Do not install the control panel where it may not accurately 
sense the relative humidity such as near HVAC supply 
registers, near exterior doors, on an outside wall, near a 
window, or near a water source. 

The installer must supply the wiring between the UA-90H and the 
control panel. Be sure to safely route the control wiring to prevent 
damage during installation. 

CAUTION 

Do not cross wires when connecting the UA-90H and the remote 
control panel or damage to the transformer may result. The remote 
controls of the UA-90H are powered by a low voltage circuit 
(24VAC) and must NEVER contact or be connected to a high voltage 
circuit. 

The control wires leaving the UA-90H and the remote control 
panels are numbered and color-coded to prevent confusion. Some 
of the control wires leaving the UA-90H may not be used with 
certain control panels and should be left unconnected with wire 
nuts taped onto the stripped ends for safety. Be sure to consult the 
electrical schematic in this manual or inside the access panel of 
the UA-90H before making control connections. 

4.3 Condensate (Water) Removal 

IMPORTANT 

A trap in the drain line is preferred, but not required for the unit to 
drain properly. Local codes may require a trap. Use care to keep the 
pipe assembly as flat to the floor as possible. Kinks and/or humps 
will prevent proper drainage. The UA-90H generates condensate. 
Install a 3/4" male nominal pipe thread adapter to the drain pan. 
It is necessary to assemble your own drain pipe assembly utilizing 
3/4" PVC pipe to get the condensate to a floor or other drain. Pipe is 
commonly available in 10’ lengths from building supply, plumbing 
or hardware stores. Grade of pitch should be 1" per 10'.  

4.3A Lifting Condensate 

An optional condensate pump kit may be installed if a lift is 
required to dispose of the condensate. The condensate pump can 
be ordered direct from the factory. See the optional parts list in 
Section 8 for information on the kit. 

4.3B Condensate Pump Kit 

An optional condensate pump kit is available from the factory for 
use with the UA-90H. Condensate is automatically pumped to a 

remote location when the water level in the pump’s reservoir rises 
to close the float switch. The pump also contains a safety float 
switch. The white leads from this switch extend from beneath the 
pump cover. This switch should be installed in series with the field 
wire that connects the blue (#5) lead from the UA-90H to the the 
control panel. If the pump fails, this switch opens the compressor 
control circuit and stops water production before the reservoir 
overflows. The UA-90H will continue to ventilate or circulate air as 
normal, but will not dehumidify until this switch closes. 

4.4 Ducting 

IMPORTANT 

Attention:  For ventilation only! Remove label and 6’’ round 
insulation from the duct prior to installing ducting for outside 
ventilation. For all other applications leave in place. 

For the ideal installation, draw air from the central part of the home 
and return it to the isolated areas of the home like the bedrooms, 
den, utility room, or family room. The ductwork of the existing 
heating system can be used to supply air to the home. If the 
existing supply goes to isolated areas of the home, discharge the 
supply of the UA-90H into the supply of the existing heating system. 
Installation of a separate supply duct to the UA-90H from a central 
area is recommended. 

4.4A Fresh Air/Supply Air 

IMPORTANT 

DO NOT draw air directly from the kitchen, laundry, or isolated 
basement.

 

You may draw air from a basement that is open to the home. All 
flexible ducting connected to the UA-90H should be UL listed. 

A short piece of flexible ducting on all UA-90H duct connections 
is recommended to reduce noise and vibration transmitted to 
rigid ductwork in the structure. Ducting the UA-90H as mentioned 
requires consideration of the following points: 

Duct Sizing: For total duct lengths up to 25’, use a minimum 10" 
diameter round or equivalent rectangular. For longer lengths, use a 
minimum 12" diameter or equivalent. Grills or diffusers on the duct 
ends must not excessively restrict airflow. 

FOR HVAC INSTALLER ONLY

4

Ultra-Aire 90H Installer’s & Owner’s Manual

5

Ultra-Aire 90H Installer’s & Owner’s Manual

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: