background image

11. Service 

CAUTION

CAUTION: Servicing the UA-90H with its high pressure 
refrigerant system and high voltage circuitry presents a health 
hazard which could result in death, serious bodily injury, and/
or property damage. Call your HVAC contractor. 

11.1 Technical Description 

The UA-90H uses a refrigeration system similar to an air 
conditioner’s to remove heat and moisture from incoming air, and 
add heat to the air that is discharged. Hot, high-pressure refrigerant 
gas is routed from the compressor to the condenser coil (See Figure 
1). The refrigerant is cooled and condensed by giving up its heat to 
the air that is about to be discharged from the unit. The refrigerant 
liquid then passes through a strainer and capillary tubing which 
causes the refrigerant pressure and temperature to drop. It next 
enters the evaporator coil where it absorbs heat from the incoming 
air and evaporates. The evaporator operates in a flooded condition, 
which means that all the evaporator tubes contain liquid refrigerant 
during normal operation. A flooded evaporator should maintain 
nearly constant pressure and temperature across the entire coil, 
from inlet to outlet. 

The mixture of gas and liquid refrigerant enter the accumulator 
after leaving the evaporator coil. The accumulator prevents any 
liquid refrigerant from reaching the compressor. The compressor 
evacuates the cool refrigerant gas from the accumulator and 
compresses it to a high pressure and temperature 

11.2 Troubleshooting 

No dehumidification, neither fan nor compressor run with fan 
switch and ventilation timer OFF. 

1. Unit unplugged or no power to outlet. 
2. Humidity control set too high or defective. 
3. Loose connection in internal or control wiring. 
4. Defective Compressor relay. 
5. Defective control transformer. 
6. Optional Condensate Pump Safety Switch open. 

No dehumidification, compressor does not run but fan runs 
with fan switch and ventilation timer OFF and humidity control 
turned to ON. 

1. Defective compressor run capacitor. 
2. Bad connection in compressor circuit. 
3. Defective compressor overload. 
4. Defective compressor. 
5. Defrost thermostat open. 
6. Optional Condensate Pump Safety Switch open. 

Fan runs with fan switch and ventilation timer OFF, but 
compressor cycles on and off. 

1.  Low ambient temperature and/or humidity causing unit to 

cycle through defrost mode. 

2. Defective compressor overload. 
3. Defective compressor. 
4. Defrost thermostat defective. 
5. Dirty air filter(s) or airflow restricted. 
6. Low refrigerant charge, causing defrost control to cycle. 
7.  Bad connection in compressor circuit. Fan does not run with 

fan switch in either position. 

Fan does not run with ventilation timer activated. Compressor 
runs briefly but cycles on & off with humidity control turned to 
ON. 

1. Loose connection in fan circuit. 
2. Obstruction prevents fan rotation. 
3. Defective fan. 
4. Defective fan relay. 
5. Defective fan capacitor. 

Fan runs with fan switch ON. Fan does not run with ventilation 
timer activated. 

1. Defective ventilation timer. 
2. Time not correct on ventilation timer. 
3. Ventilation timer set to manual and switched OFF. 
4. Defective fan switch. 

Evaporator coil frosted continuously, low dehumidifying 
capacity. 

1. Defrost thermostat loose or defective. 
2. Low refrigerant charge. 
3. Dirty air filter(s) or airflow restricted. 
4. Excessively restrictive ducting connected to unit.

FOR HVAC INSTALLER ONLY

22

Ultra-Aire 90H Installer’s & Owner’s Manual

23

Ultra-Aire 90H Installer’s & Owner’s Manual

Refrigeration System of UA-90H

Содержание Ultra Aire 90H

Страница 1: ...emoved by the evaporator coil is returned to the air stream resulting in an overall temperature increase from the incoming air Fresh Air Ventilation optional Fresh air may be ducted to the unit and re...

Страница 2: ...H Fresh Air AND Damper 8 4 6F DEH 3000 Digital Controller WITHOUT Fresh Air 8 4 7 Humidity Control Adjustment 8 4 8 Fan Filter Switch 8 4 9 Ventilation Timer 9 4 9A Setting the Time 9 4 9B Ventilation...

Страница 3: ...nel for maintenance and service DO NOT INSTALL UNIT WITH THE FRONT PANEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...e Wiring Unit location should be in an area where field wiring the remote controls low voltage to the unit will be possible n 4 1D Back Draft Damper It is recommended that a back draft damper be used...

Страница 5: ...Kit An optional condensate pump kit is available from the factory for use with the UA 90H Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to...

Страница 6: ...r 4 Exhaust fans are recommended in the bath rooms and kitchen In cold climates or areas where the outdoor dew point is low at times ventilation can be used to dehumidify the structure making the UA 9...

Страница 7: ...make up air Adjust a damper in the duct to provide the desired 4 4E Installation in a Structure with No Existing Forced Air HVAC System When installing the UA 90H in a structure that does not have a...

Страница 8: ...installed in the fresh air duct When the fan filter switch is in the OFF position the damper is closed The UA 90H will then circulate and dehumidify air to provide humidity control When the fan filte...

Страница 9: ...s on a 24 hour military time clock 4 9B Ventilation Schedule Slide the switch in the upper right hand corner to the program symbol P ON will appear to the right of the time and the number 1 will appea...

Страница 10: ...o position 6 Make the electrical connections to the terminals on the back panel as shown in the wiring diagram 7 Reassemble the front to the back panel Connect at the top first then at the bottom 8 Te...

Страница 11: ...n COM NO COM NC ON CLOSED OPEN OFF OPEN CLOSED Common uses assuming standard thermostat wiring color schemes as noted Disengage A C during dehumidification Redirect the yellow thermostat wire to the N...

Страница 12: ...ing the ON OFF button 4 Engage dehumidification operation by adjusting RH setpoint below ambient conditions a Press RH until RH setpoint is 20 b Verify Ultra Aire fan and compressor operation c Verify...

Страница 13: ...the settings If you leave the control alone and don t touch any buttons for 10 seconds the control will remember any changes made and return to home 5 3C On Off Setting Press the ON OFF button to turn...

Страница 14: ...entilating or dehumidifying while the fan is running Common reasons for operating the fan continuously are filtration and air recirculation AUTO indicates the fan will run when the control calls for d...

Страница 15: ...he indicated damper mode and return to home 5 3H Intermittent or Programmed Ventilation The system will operate the ventilation function according to the current ventilation program The control needs...

Страница 16: ...display will appear as follows 5 3I Temperature Cutout Programming Ultra Aire units produce heat when dehumidifying Depending on outside conditions the ventilation function may introduce warm air into...

Страница 17: ...transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result Control Part No 4026570 UA Base Unit Y...

Страница 18: ...lters are labeled with a MERV rating number which measures a filter s ability to trap particles ranging in size from 3 0 microns to 10 0 microns Residential filters commonly have MERV ratings of 1 12...

Страница 19: ...8 Wiring Diagrams ULTRA AIRE 90H WIRING DIAGRAM UA 90H with Humidity Fan Control 4024155 UA 90H with Ventilation Timer Humidity Fan Control 4024125 19 Ultra Aire 90H Installer s Owner s Manual...

Страница 20: ...with Filter Box 8 4026451 Condensate Pump Kit UA 90H not shown 9 4026450 Leveling Foot Kit UA 90H not shown 10 4020646 10 Backdraft Damper not shown 11 4023660 Controller Humidity 12 4023672 Duct Damp...

Страница 21: ...ator Strainer Capillary Tube Assembly FOR HVAC INSTALLER ONLY FOR HOMEOWNER ROUTINE MAINTENANCE Item Part No Description 1 4026151 14 x14 x1 Standard UA 90 H Filter 2 4024369 2 x20 x24 Filter not show...

Страница 22: ...2 Humidity control set too high or defective 3 Loose connection in internal or control wiring 4 Defective Compressor relay 5 Defective control transformer 6 Optional Condensate Pump Safety Switch open...

Страница 23: ...tor but no start capacitor or relay CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 11 5 El...

Страница 24: ...casters Step 1 Lay the unit on it s side Make sure the filter door is facing upward Note the locations of the four leveling feet and the hose adaptor Step 2 Partially screw in the leveling feet at the...

Страница 25: ...the long end into the condensate pump and the short end onto the adaptor Make sure that the hose fully covers the adaptor barbs Step 9 Adjust the height of the leveling feet to move the level bubble i...

Страница 26: ...ND EXCLUSIONS This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or insta...

Страница 27: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2006 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Отзывы: