Page 32 of 50
KNX presence detector PlanoCentro A-KNX
6.
Test modes
The PlanoCentro has two test modes.
•
Test mode presence, page 32 chapter 6.2.1
•
Test mode light, page 32 chapter 6.2.2
The test modes can only be started if the device is switched on.
6.2.1 Test presence
The test presence serves to test presence detection and parallel connection.
Activation
-
Test presence "On" with the SendoPro 868-A management remote control
-
via bus object 33
The test mode presence can be activated at anytime.
End
With subsequent restart:
-
Test presence "Off" command with the SendoPro 868-A management remote control
-
Power failure and power up
-
Automatically according to the time set with the ETS
-
via bus object 33
Without restart:
-
Activation of test light with SendoPro 868-A management remote control
LED display
Status channels
Description
On
With movement (LED on) the A channels light and H channels presence close.
Off
When the room is unoccupied (LED off) both channels open after 15 seconds.
Test response
-
Deactivate brightness measurement, light output does not react to brightness
-
The detector reacts as in fully automatic function mode even if semi-automatic is set.
-
The control type changes to switching if the control type is set to constant light control. The light is not controlled.
-
Light «On» with movement; light «Off» with absence of movement.
-
A channel light and H channel presence have a fixed switch-off delay of 15 seconds.
-
Room monitoring reacts unchanged as in normal operating mode.
-
Switch-on delay H channel and J presence is set to 0 seconds.
Commands and other parameters
The following commands are possible with the management remote control in test mode presence
-
End test presence
-
Activate test light
-
Change detection sensitivity
-
Change reducing sensitivity with room monitoring
The selected detection sensitivity (1–5), see page 16, is unchanged on activation of test presence. Sensitivity can be adjusted during the test.
The presence detector performs a reset after the end of the test mode.
6.2.2 Test light
The test light serves to monitor the brightness level (brightness threshold).
Activation
-
Test light "On" with the SendoPro 868-A management remote control
-
via bus object 34
Test light can be activated at anytime.
End
With subsequent restart:
-
Test light "Off" with the SendoPro 868-A management remote control
-
Power failure and power up
-
Automatically according to the time set with the ETS
-
via bus object 34
Without restart:
-
Activation of test presence with SendoPro 868-A management remote control