Page 14 of 50
KNX presence detector PlanoCentro A-KNX
Object
Object name
Function
Description
Object 25
Object 26
IR external
channel 1
IR external
channel 1
Switching
Brighter/darker
If an IR group address is allocated to the <Switching/dimming external 1> parameter,
objects 25 and 26 assume the following function as soon as a command is received by
the selected IR group address:
Briefly pressing the
/
push buttons causes a 0 or 1 telegram to be sent via object
25 switching. Holding down the
push button causes "dim brighter" to be sent via
object 26 and stop when released. Holding down the
push button causes "dim
darker" to be sent via object 26 and stop when released.
Object 27
Object 28
IR external
channel 2
IR external
channel 2
Switching
Brighter/darker
If an IR group address is allocated to the <Switching/dimming external 2> parameter,
objects 27 and 28 assume the same function as with objects 25/26 as soon as a com-
mand is received by the selected IR group address:
Object 29
Object 30
IR external
channel 1
IR external
channel 1
Blinds Up / Down
Lamella
Open / Closed
If an IR group address is allocated to the <Blinds external 1> parameter, objects 29 and
30 assume the following function as soon as a command is received by the selected IR
group address:
Briefly pressing the
/
push buttons causes a 0 or 1 telegram to be sent via object
lamella open/closed. Holding down the
/
push buttons causes a 1 or 0 telegram to
be sent via object blinds up/down.
Object 31
Object 32
IR external
channel 2
IR external
channel 2
Blinds Up / Down
Lamella
Open / Closed
If an IR group address is allocated to the <Blinds external 2> parameter, objects 29 and
30 assume the following function as soon as a command is received by the selected IR
group address:
Briefly pressing the
/
push buttons causes a 0 or 1 telegram to be sent via object
lamella open/closed. Holding down the
/
push buttons causes a 1 or 0 telegram to
be sent via object blinds up/down.
Object 33
Test mode presence Start / stop
An ON telegram activates the presence test mode for the duration of the configured
time.
See page 32 chapter 6.2.1 for a description of the presence test mode
An OFF telegram terminates the presence test mode early.
Object 34
Test mode bright-
ness
Start / stop
An ON telegram activates the test mode brightness for the duration of the configured
time.
See page 32 chapter 6.2.2 for a description of the test mode brightness
An OFF telegram terminates the test mode brightness early.
Object 35
Diagnosis
Status
Information on faulty or non-compliant data received is available via object 35.
The object is not sent automatically. It must be actively read and it contains an error
code:
Bit num-
ber
Error
0
ETS parameter invalid
1
The combination of brightness level and room correction factor is invalid.
2
The combination of alternative brightness level and room correction
factor is invalid.
3
Brightness level via bus value is invalid.
4
Alternative brightness level via bus value is invalid.
5
Teach-in not possible (current lux brightness level beyond 5..2000 lux)
6
The brightness level with "measurement off" setting is not possible with
constant light control.
See page 39 chapter 8.1 for details of error codes
The error is deleted after 30 minutes. The object must be actively requested. If a new,
correct brightness level is received by command, the status is set to ok (all bits = 0).