Page 16 of 50
KNX presence detector PlanoCentro A-KNX
2.4 Parameters
2.4.1 General
Parameter name
Values
Application
Operating mode
Master
A Master is capable of lighting control (switching or constant light control) and relaying the
presence information.
Slave Slaves are used to extend the detection area. They supply presence information to the
Master.
The < Cyclic time parallel circuit operation > parameter is displayed.
See information on parallel connection in chapter 4 page 29.
Master operating mode
Single unit
operation
Presence detector works as independent device.
Parallel connection Parallel connection: If required, the detection area can be extended by connecting additio-
nal detectors as "Slaves" with a "Master in parallel connection" or a number of "Masters
in parallel connection" can be connected with each other.
The < Cyclic time parallel circuit operation > parameter is displayed.
Parallel connection
cycle time
30 seconds
1 minute
2 minutes
4 minutes
Each detector sends a maximum of two ON telegrams per minute on detection of move-
ment. The interval between two telegrams can be set at up to 4 minutes to reduce the
number of telegrams.
Please note, the interval between two trigger telegrams is always shorter than the switch-
off delay times.
Automatically end test
mode after
2 –60 mins
30 mins
An activated test mode will automatically be terminated after expiry if the set time.
See page chapter 6 for description of the test modes.
Parameter settings
with download
The setting affects the following parameters:
-
Brightness level A channel light
-
Room correction factor A channel light
-
Alternative brightness level A channel light
-
Detection sensitivity (PIR)
-
Reduction of detection sensitivity when monitoring
overwrite
via download
The relevant parameter values (see above) in the presence detector are overwritten. Settings
amended with the SendoPro management remote control or vis bus object are lost.
The parameters set in the ETS are accepted.
unchanged
via download
The relevant parameter values (see above) in the presence detector are unchanged. Settings
amended with the SendoPro management remote control or vis bus object are retained.
Detection sensitivity
1–5 The detector has 5 sensitivity increments. Sensitivity also applies during the testing modes.
The setting can also be adjusted using the SendoPro management remote control.
By selecting the operation mode test presence, the set sensitivity increment is not changed.
The parameter can be changed during presence tests.
1 very insensitive
2 insensitive
3 standard
4 sensitive
5 very sensitive
3 standard
The basic setting is the middle increment (3).
Reduction of detection
sensitivity when room
monitoring
1–3 In order to prevent false alarms, the sensitivity can be reduced in stages relative to the basic
detection sensitivity. The setting can also be adjusted using the SendoPro management
remote control.
1 less
2 standard
3 intense
2 standard
The basic setting is the middle increment (2).