Page 27 of 50
KNX presence detector PlanoCentro A-KNX
Parameter name
Values
Application
Output value scene 1,
light A
Off, On
Off , 1 % – 100 %
Value of scene 1, A channel in switching mode.
Value of scene 1, A channel in constant light control.
Output value scene 2,
light A
Off, On
Off , 1 % – 100 %
Value of scene 2, A channel in switching mode.
Value of scene 2, A channel in constant light control.
Output value scene 1,
light B
Off, On
Off , 1 % – 100 %
Value of scene 1, B channel in switching mode.
Value of scene 1, B channel in constant light control.
Output value scene 2,
light B
Off, On
Off , 1 % – 100 %
Value of scene 2, B channel in switching mode.
Value of scene 2, B channel in constant light control.
2.4.15 Disabling light channels with external scenes
Without disabling via external scenes
If a scene number is sent to the actuator and thereby influences the lighting group controlled by the presence detector, the presence detector
is not disabled and continues controlling.
With disabling via external scenes
The receipt and concurrence of a scene number makes it possible to disable the presence detector and continue to influence the behaviour.
The presence detector can be disabled by a determinate maner:
-
For a defined length of time
-
Until the presence detector is enabled
See parameter <Validity of disabling>
Parameter name
Values
Application
1. Scene number for disabling
2. Scene number for disabling
3. Scene number for disabling
4. Scene number for disabling
5. Scene number for disabling
6. Scene number for disabling
7. Scene number for disabling
8. Scene number for disabling
The presence detector can be disabled using 8 different scene numbers.
Inactive
No scene number has been defined, which disables the presence
detector.
1–63 The presence detector is disabled if a received scene number
corresponds to a defined scene number.
Push button operation is still possible.
64 The light channels are enabled on receipt of scene number 64 on bus
object 14.
Validity of disabling
1 h – 12 h
4 h
The presence detector remains disabled during the set time.
Manual enabling is possible at any time:
-
Receipt of scene number 64 on bus object 14
-
Enable command of light channels on bus object 11
Until enabled Light channels enabled via:
-
Receipt of scene number 64 on bus object 14
-
Enable command of light channels on bus object 11
2.4.16 Telegram converter
Parameter name
Values
Application
Output value
0–255
1
If telegrams, regardless of values, are received by the converter inputs
(bus objects 36-38), bus object 39 sends the set output value. The
output value is sent every time a telegram is received at the inputs.