background image

Page 1 of 50

1103065001 / 06.2011 © Theben AG

KNX presence detector PlanoCentro A-KNX

KNX manual

Application description

KNX presence detector

PlanoCentro A-KNX

Содержание PlanoCentro A-KNX

Страница 1: ...Page 1 of 50 1103065001 06 2011 Theben AG KNX presence detector PlanoCentro A KNX KNX manual Application description KNX presence detector PlanoCentro A KNX ...

Страница 2: ...8 H channel presence 23 2 4 9 Disabling function presence 24 2 4 10 J channel presence 24 2 4 11 J channel disabling function 25 2 4 12 M channel room monitoring 25 2 4 13 Remote control 26 2 4 14 Scenes 26 2 4 15 Disabling light channels with external scenes 27 2 4 16 Telegram converter 27 3 Manual operation with push buttons 28 3 1 Manual operation with switching control type 28 3 2 Manual opera...

Страница 3: ...rnal light channels 36 7 3 4 Two presence detectors with one and two internal light channels 37 8 Troubleshooting 38 8 1 Evaluation of error codes diagnosis bits 39 9 Appendix 40 9 1 Typical applications 40 9 1 1 Presence and brightness dependent switching of light 40 9 1 2 Presence and brightness dependent switching of light additional manual override via push button 41 9 1 3 Presence and brightn...

Страница 4: ...and switch off delay Separate channel for room monitoring with cyclical report object Parallel connection Master Slave for complete coverage of large areas Parallel connection Master Master for several lighting groups with separate light measurement but joint presence detection Separate disable objects for light and presence channel Scene control with two scenes Scene functionality with scene numb...

Страница 5: ...n type PlanoFix E installation frame Ceiling cut out 100 x 100 mm 1 mm Ceiling strength up to approx 26 mm Flush mounted installation concrete ceiling Installation type PlanoFix U flush mounted junction box Flush mounted junction box 115 x 115 x 100 mm Agro Kaiser 9908 01 1298 07 PlanoFix U installation plate Metal 118 x 118 mm Item numbers PlanoCentro EWH A KNX integrated installation set white 2...

Страница 6: ...ht stationary persons moving persons 2 0 m 20 m2 4 5 m x 4 5 m 36 m2 6 0 m x 6 0 m 0 5 m 2 5 m 36 m2 6 0 m x 6 0 m 64 m2 8 0 m x 8 0 m 0 5 m 3 0 m 49 m2 7 0 m x 7 0 m 81 m2 9 0 m x 9 0 m 1 0 m 3 5 m 64 m2 8 0 m x 8 0 m 100 m2 10 0 m x 10 0 m 1 0 m Detection area with an installation height of 3m side view and layout o 89 83 5 73 89 83 62 5 112 123 6 118 107 r 6 6 seated persons moving persons ...

Страница 7: ...or the lighting control of channel B light The settings are based on A channel light G channel send brightness value Settings for the current brightness value via the bus H channel presence Channel for the presence dependent control of other systems such as heating air conditioning Disabling function presence Settings for disabling of H channel presence J channel presence Channel for the presence ...

Страница 8: ... H channel presence Switching 1 bit 3 3 17 J channel presence Send value 1 byte 3 3 18 H J channel presence Disable enable 1 bit 3 3 19 M channel room monitoring Message 1 bit 3 3 20 M channel room monitoring Confirmation 1 bit 3 3 21 M channel room monitoring Sabotage cyclically 1 bit 3 3 22 M channel room monitoring Enable 1 bit 3 3 23 Parallel connection Trigger input output 1 bit 3 3 3 24 Inpu...

Страница 9: ... detector PlanoCentro A KNX 2 3 2 Explanation of the flags Flag Flag name Description C Communication Object can communicate R Read Object value can be read ETS display etc W Write Object can receive T Transmit Object can send ...

Страница 10: ... request for the current dimming value to the actuator via object 3 Control with 1 byte telegrams to object 2 starts from this dimming value Start control with ON telegram An On telegram is sent via object 0 on detection of movement and insufficient bright ness The actuator switches on and dims up to the configured value on the actuator The presence detector sends a request for the current dimming...

Страница 11: ... error occurs object 35 provides the information for error diagnosis with a 1 byte value See Diagnosis page 14 Object 7 B channel light Switching If two switching outputs are used object 4 provides brightness dependent switching for B channel Function see object 0 A channel light Switching Object 7 Object 8 Object 9 Object 10 B channel light B channel light B channel light B channel light Switchin...

Страница 12: ...minimum change in brightness The 2 byte telegrams via object 15 provide visualisation of a brightness value but should not be used for an external control The use of the presence detector s internal constant light control is recommended for that sort of control The brightness measurement can be adapted to the conditions in a room with the room correction factor See page 19 chapter 2 4 3 2 3 4 Char...

Страница 13: ...ne presence detector In configuring the detector it is only visible as a Master in parallel connec tion or as a Slave There are two possible types of switching Master Slave parallel connection A Master receives the movement information from se veral Slaves in the room and switches or controls the lighting as required The advantage is uniform switching with a defined brightness value For applicatio...

Страница 14: ...ess is allocated to the Blinds external 2 parameter objects 29 and 30 assume the following function as soon as a command is received by the selected IR group address Briefly pressing the push buttons causes a 0 or 1 telegram to be sent via object lamella open closed Holding down the push buttons causes a 1 or 0 telegram to be sent via object blinds up down Object 33 Test mode presence Start stop A...

Страница 15: ...Telegram converter See page 17 If telegrams regardless of value are received at the converter inputs object 39 sends the set value of the Output value parameter The set Output value is sent every time a telegram is received at the inputs See page 27 chapter 2 4 16 Object 37 Input converter 4 bit Receive Object 38 Input converter 1 byte Receive Object 39 Output converter 1 byte Send value ...

Страница 16: ...he set time See page chapter 6 for description of the test modes Parameter settings with download The setting affects the following parameters Brightness level A channel light Room correction factor A channel light Alternative brightness level A channel light Detection sensitivity PIR Reduction of detection sensitivity when monitoring overwrite via download The relevant parameter values see above ...

Страница 17: ...esence detector stops controlling See page 27 chapter 2 4 15 Inactive The Disabling light channels with external scenes parameter page is faded out The response to external scenes is switched off active The Disabling light channels with external scenes parameter page is faded in Telegram converter Inactive The Telegram converter parameter page is faded out active The telegram converter parameter p...

Страница 18: ... The lighting is switched off on completion of the switch off delay time or with sufficient brightness if the lighting is already dimmed to the minimum The second B channel light can be controlled with a difference in brightness Note If the two A B channels light are active both channels will be in control or switching operating mode It is not possible to combine control and switching operating mo...

Страница 19: ... type switching The brightness level defines the minimum required bright ness The current prevailing brightness is measured below the presence detector If the prevailing brightness is below the set point the light switches on as soon as a presence is detected Control type constant light control The defined brightness level is set via the control dimming of the lights objects 1 3 and 8 9 5 2000 lx ...

Страница 20: ...m and it is only occupied for up to 30 seconds the light goes off after 2 minutes Monitoring applies in combination with the self learning switch off delay time Short presence is also applied if a push button is used to switch on Selecting brightness level Inactive Only the brightness level base is available as a brightness level Active A second alternative brightness level can be configured Both ...

Страница 21: ...increment of the sent dimming value Standard Behaviour is set to its optimum level The change happens gradually and is almost imperceptible Average Fast The change happens more quickly The change happens more quickly Standby light Inactive The standby function for A B channels light is not available Active The standby function for A B channels light is available and the parameters are faded in Sta...

Страница 22: ...ls light are enabled via an OFF telegram After enabling the detector sends the current status and continues the constant light control with OFF telegram Both light outputs are disabled with OFF telegram and enabled with ON telegram Behaviour at start of disabling ON telegram OFF telegram no telegram No telegram is sent at the start of the disabling An ON telegram is sent at the start of the disabl...

Страница 23: ...ameter name Values Application Switch on delay time presence Inactive 10 s 30 mins An inactive switch on delay means the presence channel switches immediately on detection of movement A switch on delay of 10 seconds to 30 minutes can be set for the presence channel The presence channel does not switch immediately on detection of movement but only after completion of the switch on delay The switch ...

Страница 24: ...m No telegram is sent at the start of the disabling Send ON telegram An ON telegram is sent at the start of the disabling The detector sends its current status after the enable process is completed Send OFF telegram An OFF telegram is sent at the start of the disabling The detector sends its current status after the enable process is completed 2 4 10 J channel presence Switch on delay and switch o...

Страница 25: ...N telegram in cyclical intervals providing there is no confirmation Behaviour at start end of presence Send ON and OFF telegram Both ON and OFF telegrams are sent on selection of the switching On Off Type of report Only send ON tele gram The OFF telegram is not sent at the end of presence Switch off delay time room monitoring 30 s 30 mins 5 mins Switch off delay time is restarted with each movemen...

Страница 26: ... On Off with switching operating mode percentage values with constant light control End Absent ON OFF with the SendoClic user remote control internal scenes The Define scenes with parameter is faded in The scenes can be called up by pressing the scene buttons on the Sen doClic user remote control or via a telegram to the scene object Send scene The Scene number key scene 1 and Scene number key sce...

Страница 27: ...fined length of time Until the presence detector is enabled See parameter Validity of disabling Parameter name Values Application 1 Scene number for disabling 2 Scene number for disabling 3 Scene number for disabling 4 Scene number for disabling 5 Scene number for disabling 6 Scene number for disabling 7 Scene number for disabling 8 Scene number for disabling The presence detector can be disabled ...

Страница 28: ... time OFF telegram The lighting remains switched off while the room is occupied The detector returns to normal switching mode after the room is vacated and after expiry of the switch off delay 3 2 Manual operation with constant light control control type If the lighting is manually operated using the constant light control control type the presence detector shows the following behaviour Push butto...

Страница 29: ...nnection can be linked to each other Presence detection is completed jointly while light measurement parameter settings and lighting control are individually processed by each Master This produces more light outputs with their own light measurement but with joint presence detection 4 3 Telegram load using parallel connection With parallel connection each master sends in parallel connection and eac...

Страница 30: ...g ned to the lux meter value measured in the area below the presence detector See parameter Room correction factor page 19 The standard value of the room correction factor is 0 3 and is suitable for most applications The sensitivity of the light sensor to brightness changes will be affected when adjusting the room correction factor Procedure 1 Determine the lux values below the presence detector w...

Страница 31: ...lue for example Theben DMG 2 S DME 2 S Universal dimming actuator Theben SMG 2 S SME 2 S control device for dimmable electronic series devices They are connected with the PlanoCentro A KNX as follows to ensure perfect constant light control Actuator group addresses C R W T Act PlanoCentro A KNX group addresses 0 On Off 10 0 1 3 3 Leave default 0 Switching 10 0 1 1 Dimming 10 0 2 3 3 1 Brighter dar...

Страница 32: ...s set The control type changes to switching if the control type is set to constant light control The light is not controlled Light On with movement light Off with absence of movement A channel light and H channel presence have a fixed switch off delay of 15 seconds Room monitoring reacts unchanged as in normal operating mode Switch on delay H channel and J presence is set to 0 seconds Commands and...

Страница 33: ...rformance characteristics The SendoClic infrared remote control makes it easy to switch and dim lighting using the PlanoCentro A KNX presence detector SendoClic has two channels for controlling lighting groups blinds or external channels with switching and dimming SendoClic provides the option of saving two different lighting scenes which can be retrieved anytime at the key press 7 2 Combination o...

Страница 34: ... one presence detector using a SendoClic remote control A channel light of the presence detector is controlled by channel 1 on the SendoClic B channel light of the presence detector is controlled by channel 2 on the SendoClic Devices PlanoCentro A KNX Order no 205 9 SendoClic Order no 907 0 690 Overview Master Channel IR group addr ON OFF SCENE 2 1 A channel light B channel light I II Parameters P...

Страница 35: ...diverted in the room and therefore received by other presence detectors The blinds are controlled via the presence detector Master 2 using channel 2 on SendoClic Channel 2 commands are ignored by Master 1 Devices PlanoCentro A KNX Order no 205 9 SendoClic Order no 907 0 690 Overview IR group addr Channel Master 1 Master 2 Channel IR group addr I A channel light ON OFF SCENE 2 1 A channel light Ext...

Страница 36: ...annels are not mutually influenced by the SendoClic commands Devices PlanoCentro A KNX Order no 205 9 SendoClic Order no 907 0 690 Overview IR group addr Channel Master 1 Master 2 Channel IR group addr I A channel light ON OFF SCENE 2 1 A channel light II Parameter PlanoCentro A KNX Master 1 Parameter page Parameter Setting Remote control Switching Dimming A I Scenes Scene control internal scenes ...

Страница 37: ...nfluenced by the commands from the two SendoClics Devices PlanoCentro A KNX Order no 205 9 SendoClic Order no 907 0 690 Overview IR group addr Channel Master 1 Master 2 Channel IR group addr I A channel light ON OFF SCENE 2 1 ON OFF SCENE 2 1 A channel light B channel light II III SendoClic 1 SendoClic 2 Parameter PlanoCentro A KNX Master 1 Parameter page Parameter Setting Remote control Switching...

Страница 38: ...and room correction factor is invalid Diagnosis bit no 1 The combination of brightness level and room correction factor is invalid The parameters are outside the setting limits see parameter Continuation of room correction factor page 20 Diagnosis bit no 2 The combination of alternative bright ness level and room correction factor is invalid The parameters are outside the setting limits see parame...

Страница 39: ...1 1 1 0 0 1 58 3A 0 1 1 1 0 1 0 59 3B 0 1 1 1 0 1 1 60 3C 0 1 1 1 1 0 0 61 3D 0 1 1 1 1 0 1 62 3E 0 1 1 1 1 1 0 63 3F 0 1 1 1 1 1 1 64 40 1 0 0 0 0 0 0 Telegram Diagnosis bit Dec Hex Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 65 41 1 0 0 0 0 0 1 66 42 1 0 0 0 0 1 0 67 43 1 0 0 0 0 1 1 68 44 Not used 1 0 0 0 1 0 0 69 45 1 0 0 0 1 0 1 70 46 1 0 0 0 1 1 0 71 47 1 0 0 0 1 1 1 72 48 1 0 0 1 0 0 0 ...

Страница 40: ... detector is switching lights on if a room is occupied and there is insufficient natural daylight The lighting is automatically switched off if the room is vacated or the share of daylight increases Devices PlanoCentro A KNX Order no 205 9 RMG 8 S KNX Order No 493 0 220 Overview Links PlanoCentro A KNX RMG 8 S Comments No Object name No Object name 0 A channel light Switching 0 RMG 8 S channel C1 ...

Страница 41: ...cupied Devices PlanoCentro A KNX Order no 205 9 RMG 8 S KNX Order No 493 0 220 Overview Links PlanoCentro A KNX RMG 8 S Comments No Object name No Object name 0 A channel light Switching 0 RMG 8 S channel C1 Switching lighting on and off any KNX push button RMG 8 S Comments No Object name No Object name x e g key 1 0 RMG 8 S channel C1 Manual switching on and off via push button Parameter PlanoCen...

Страница 42: ... name 0 A channel light Switching 0 GM RMG 8 S channel C1 Switching lighting near the window on and off 7 B channel light Switching 10 GM RMG 8 S channel C2 Switching lighting in the interior of the room on and off Parameter PlanoCentro A KNX Parameter page Parameter Setting General Operating mode Master Master operating mode Single unit operation Channel functions A channel light active B channel...

Страница 43: ... KNX Order no 205 9 Mix combination RMG 8 S upgrade module HME 4 Order No 493 0 220 491 0 211 Ramses 713 S KNX Order no 713 9 201 Overview Links PlanoCentro A KNX MiX combination Comments No Object name No Object name 0 A channel light Switching 0 GM RMG 8 S channel 1 Switching lighting on and off PlanoCentro A KNX RAM 713 S Comments No Object name No Object name 16 H Channel presence Switching 4 ...

Страница 44: ...Parameter Setting Operating mode Objects for determining the operating mode new Operating mode presence window status Operating mode after reset Standby Presence sensor type to obj 4 Presence detector Heating control 1 Type of control Continuous control MiX combination RMG 8 S and upgrade module HME 4 Parameter page Function Setting General Type of basic module 1 upgrade module 2 upgrade modules 2...

Страница 45: ... SMG 2 S Channel 1 Switching ON OFF 1 A channel light Brighter darker 1 GM SMG 2 S Channel 1 Brighter darker 2 A channel light Send value 2 GM SMG 2 S Channel 1 Dimming value 3 A channel light Feedback value 5 GM SMG 2 S Channel 1 Feedback in Parameter PlanoCentro A KNX Parameter page Parameter Setting General Operating mode Master Master operating mode Single unit operation Channel functions A ch...

Страница 46: ...he lighting must always be switched on by hand the detector does not switch the lighting on independently Devices PlanoCentro A KNX Order no 205 9 SMG 2 S Order No 491 0 273 Overview Links PlanoCentro A KNX SMG 2 S Comments No Object name No Object name 0 A channel light Switching 0 GM SMG 2 S channel 1 Switching ON OFF 1 A channel light Brighter darker 1 GM SMG 2 S channel 1 Brighter darker 2 A c...

Страница 47: ...an office Switch off delay time 10 mins Dimmer SMG 2 S Parameter page Parameter Setting SMG 2 S channel 1 C1 1 Minimum brightness 5 Dimming time from 0 to 100 10 seconds When receiving a dimming value scene no Soft on KNX push button example Parameter page Parameter Setting Rocker 1 left Telegram on pressing the key On Telegram when released no telegram Rocker 1 right Telegram on pressing the key ...

Страница 48: ...value 5 GM SMG 2 S channel 1 Feedback 7 B channel light Switching 10 GM SMG 2 S channel 2 Switching ON OFF 8 B channel light Brighter darker 11 GM SMG 2 S channel 2 Brighter darker 9 B channel light Send value 12 GM SMG 2 S channel 2 Dimming value 10 B channel light Feedback value 15 GM SMG 2 S channel 2 Feedback Parameter PlanoCentro A KNX Parameter page Parameter Setting General Operating mode M...

Страница 49: ...inks PlanoCentro A KNX RMG 8 S Comments No Object name No Object name 0 Output light A Switching 0 GM RMG 8 S channel C1 Switching lighting on and off PlanoCentro A KNX Slaves PlanoCentro A KNX Master Comments No Object name No Object name 23 Parallel connection Trigger input output 23 Parallel connection Trigger input output Connection between Master and Slave Parameter PlanoCentro A KNX Master P...

Страница 50: ...PlanoCentro A KNX Order no 205 9 RMG 8 S Order No 490 0 220 Overview Links PlanoCentro A KNX RMG 8 S Comments No Object name No Object name 0 Output light A Switching 0 GM RMG 8 S channel C1 Switching lighting on and off PlanoCentro A KNX PlanoCentro A KNX Comments No Object name No Object name 23 Parallel connection Trigger input output 23 Parallel connection Trigger input output Connection betwe...