Block Diagram of the Tiger 320 Series Software and Hardware Structure

RESIDENT TIMER 1
RESIDENT TIMER 2

Runs ONLY if selected on CH3,
or CH4.   Resolution 1 sec

I2C 
BUS

LOGIC I/O

FROM 

MODULES

Prescaler
Channel 1 & 2

17 BIT ON BOARD

DUAL SLOPE A to D

REF IN

CHANNELS

RESULT

CHANNEL

1

2

3

4

CHANNELS 1

2

1

2

3

4

1

R

R

2

3

4

1

R

D

D

2

3

4

1

R

DEFAULT

DISPLAY

CHANNEL

DEFAULT

DISPLAY

CHANNEL

2

3

4

DISPLAY FORMATTING

 

I2C

MICRO

Sigma Delta

A to D

16 to 24 Bit

Signal

Conditioning

REF

SSR SSR

REF

Sig

Con

SMART MODULES WITH MULTICHANNEL INPUTS,

AN ON-BOARD A TO D CONVERTER,

MICROPROCESSOR, AND TWO 
SOLID STATE RELAY OUTPUTS

Signal

Conditioning

MULTI-INPUT MODULES

W/DIGITAL SCALING

MUX

REF

PULSE

Signal

Conditioning

SINGLE INPUT MODULES

WITH ANALOG SCALING

REF

ZERO

SPAN

Signal

Conditioning

REF

RAW DATA                   

ANALOG, DIGITAL

                                       

AND LOGIC I/O

MACRO PROCESSING

DATA LOGGING

Manual or auto, Up to 4000 

samples, Date and Time 

stamp, endless loop record, 

Burst downloading

SERIAL COMMUNICATION

Read and write into all registers

ASCII, MODBUS,
Meter TO Meter Communication,
ETHERNET (TCP/IP), Epson Compatible
Serial Printer Driver

SETPOINTS

Up to 6 relay, SSR,
TTL or open collector.
PID, deviation, trigger, pulse,
tracking, hysteresis, latching,
timer modes, reset,
High/low/deviation activation

TOTALIZER 1
TOTALIZER 2

Two independent totalizers

Linearizing

4 Tables of 32 Points each
or 1 Table of 125 Points

Internal System Clock

Downloads from Real Time Clock
or starts from 12:00 on power up.
Can be displayed on CH3, CH4

Optional Real-time clock
with date and time stamp

Rear Pins

Hold, Test, Lock & Capture.

The Lock, Hold and Capture 

pins can be reprogrammed
for use as Digital Logic I/O pins.

 

ANALOG OUTPUT

Voltage or current, 

single or dual

PLUG IN OPTO-ISOLATED
I/O 6 IN 6 OUT OR 6 IN 16 OUT

DISPLAY DRIVE

SMART MODULES WITH AN ON BOARD

MICROPROCESSOR AND TWO SOLID STATE

RELAY OUTPUTS WITH PULSE, OR QUADRATURE

ENCODER INPUTS FOR COUNTING, FREQUENCY OR POSITION

I2C

MICRO

Signal

Conditioning

SSR SSR

REF

Sig

Con

Signal

Conditioning

 

Cross Channel Math 

 1+2, 1-2, 1x2, 1/2, 1=R

RESET 

with UP/DOWN

Peak, Valley,

Tare, Totalizers

VIEW MODE

to view 

selected

function values 

P and UP Buttons

to enter setup

menu.

P and DOWN 

Buttons to enter 

setpoint menu. 

PROGRAM

BUTTON

MACRO_

PROCESSING

Including

EDIT MACRO

F1_BUTTON

MACRO_

PROCESSING

F2_BUTTON

MACRO_

PROCESSING

F3_BUTTON

MACRO_

PROCESSING

ON DEMAND
FUNCTIONS
Hold down the
 PROGRAM 
button for 4 secs 
to initiate Auto 
tare, Auto 
Calibration,
Manual Loader or
Input Channel 
Compensation

PROGRAM LOCK 

If Program lock is ON values are 

displayed, but cannot be changed

SETPOINT LOCK 

If Program lock is ON values are 

displayed, but cannot be changed

Prog

F1

F2

F3

RESULT PROCESSING

of Cross Channel Math

Select data source for

 

OUTPUT PROCESSING

Select data source for: Setpoint 1, 2, 3, 4, 5, 6; 
Analog output 1, 2; Data logging

                                        

Select data source for 

DISPLAY PROCESSING

Select data source for: 
Display 1 (Default Display Channel D), Display 2, 
Display 3, Peak, Valley, Totalizer 1, Totalizer 2,

        

AVERAGING, 
CALIBRATION (SCALE and OFFSET),
INVERSE OF INPUT, LINEARIZATION, 
LOG OF INPUT (Bargraph display only)
RTD, SAMPLE RATE, SMART AUTO ZERO,
SQUARE ROOT,  THERMOCOUPLES

DECIMALS, , RIGHT HAND CHARACTER, AND ROUNDING 
FOR CH1, 2, 3, 4, RESULT AND DEFAULT DISPLAY

CUSTOM TEXT FOR CH1, 2, 3, 4, RESULT, PEAK, VALLEY,
TOTALIZER 1, TOTALIZER 2, SP1, SP2, SP3, SP4, SP5, SP6

DIGITAL PROCESSING

Select from R, 1, 2, 3, 4, Totalizer 1, 2, Peak, 
Valley, Tare or any usable registers from 1 to 244

        

Select from R, 1, 2, 3, 4, Totalizer 1, 2, Peak,
Valley, Tare or any usable registers from 1 to 244

        

Code1

SPC_1 to 6

SPC_1 to 6

Code1

Code7

   

Code2

Code4

Code5

Code6

Code8

CAL

CAL

CAL

CAL

CAL

CAL

CAL

CAL

Linearization

24 bit registers in EEPROM that store 
the four 32 point LIN tables.

 

Registers 257 to 512

OPERATING SYSTEM USE ONLY

DO NOT write to these registers, as 
any alteration to their data may make
the meter inoperative.

Registers 1125 to 2048

OPERATING SYSTEM USE ONLY

DO NOT write to these registers, as 
any alteration to their data may make
the meter inoperative.

Registers 4097 to 5120

Multi function, multi type Registers 
that may only be accessed through 
the serial port or by macros. Their 
functions are detailed in the Register 
Supplement.

Registers 513 to 1124

Macro Code Storage

16 bit unsigned. In Flash RAM

Registers 2049 to 4096

16 bit unsigned. May be 
accessed by macros or 
Serial Port.

Registers 5120 to 6144

Code9

Code5

Code6

FLASH

Result of Cross

Channel Math

AVERAGING, CALIBRATION (SCALE & OFFSET),  
INVERSE of R, LOG OF R (Bargraph display only)
 

 

       LINEARIZING of R, 

 

 

       SMART AUTO ZERO,

                                          SQUARE ROOT of R,

SP1

SP2

SP3
SP4

SP5

SP6

Registers 1 to 244

Registers from 1 to 244 may be selected

manually as a data source for setpoint 

or output processing. However only 

those registers shown below contain 

data applicable for use as data source.

Setpoints

6 to 11- SP1,2,3,4,5,6 value

65 to 70- SP1,2,3,4,5,6 Hysteresis,

71 to 76- delay on make SP1,2,3,4,5,6

77 to 82-  delay on break SP1,2,3,4,5,6

Input Channels

18,19,20,41,42- Raw Result,CH1,2,3,4

21 to 23,43,44- Scaled Result,CH1,2,3,4

45,46- Prescaler CH1,2

 

Smart modules

54 to 60- Smart Output 1,2,3,4,5,6,7

Analog Outputs

83, 84 - Analog Output 1 & 2

Variables (Used with Macro Only)

85 to 94 - Variable 1 to Variable 10

Timers

95 & 96 - Timer 1, 2

Real time Clock

213 to 219 - Real Time Clock

Auto Zero Offset

227 to 231 - Auto Zero Offset for Result,

CH1, CH2, CH3 & CH4

Operating System 

NOT USABLE as a data source. 

15,38,47,48,52,53,61-64,123-128,140,

141,160,161,234-244

6144 REGISTERS

  

Registers are comprised of 8, 16 or 

32 bit signed, unsigned or floating 

point registers, implemented in either 

Flash RAM, RAM, FeRAM, EEPROM 

or NVRAM (Real time clock option).

   See the Register Supplement for 

detailed information on ALL registers

   All registers may be accessed, and 

read or written to via the serial port, 

and by user developed macros.

   

  The registers used for the operating 

system should not be written into, as

modification of their data may render

the meter inoperative.

LOG BARGRAPH DISPLAY, dB DISPLAY, OCTAL.

BRIGHTNESS, ANNUNCIATORS, TREND

SCALE, OFFSET FOR CH1, 2, 3, 4 AND RESULT

A macro can access all functions and read
and write into all registers. Macro Timer1,
Macro Timer2 have 0.1 second resolution.
Macros allow a user to customize a meter
for a specific application using the Tiger 320
Development System. Macros may be locked
to prevent access by anyone.

ANALOG, DIGITAL
AND LOGIC I/O

Содержание Tiger 320 GI-50E

Страница 1: ...ent 5 digit Programmable Meter Controller PMC with modular outputs input signal conditioning and advanced software features for monitoring measurement control and communication applications GI 50E GI 50T Programmable Meter Controllers Tiger 320 Series PMCs 5 Digit 1 LEDs in a 9 32 DIN Case Serial output options include RS 232 RS 485 ModBus or direct meter to meter communications Single or dual 16 ...

Страница 2: ...y configurable hysteresis on and off delays one shot pulse and repeat timers latching dual PID setpoint tracking resetting of registers initiating of logging and printing Signal Conditioning Functions Averaging smart filter rounding square root auto zero maintenance Timer Timer functions supported in either time up time down or real time clock modes Totalizer Two totalizers for running total and b...

Страница 3: ... or reverse Analog Output Specifications Accuracy 0 02 FS Resolution 16 bit Delta Sigma D A provides 0 4µA on current scaling 250µV on voltage scaling Compliance 500Ω maximum for current output 500Ω minimum for voltage output Update Rate Typical 7 per second Step Response Typical 6msec to a display change Scalable From 1 count to full scale Outputs continued Seven I O Modules Plug into any carrier...

Страница 4: ...ET INVERSE OF INPUT LINEARIZATION LOG OF INPUT Bargraph display only RTD SAMPLE RATE SMART AUTO ZERO SQUARE ROOT THERMOCOUPLES DECIMALS RIGHT HAND CHARACTER AND ROUNDING FOR CH1 2 3 4 RESULT AND DEFAULT DISPLAY CUSTOM TEXT FOR CH1 2 3 4 RESULT PEAK VALLEY TOTALIZER 1 TOTALIZER 2 SP1 SP2 SP3 SP4 SP5 SP6 DIGITAL PROCESSING Select from R 1 2 3 4 Totalizer 1 2 Peak Valley Tare or any usable registers ...

Страница 5: ...Apr 08 2016 GI 50 320 DS NZ308 _UL April 2016 Page 5 Texmate Inc Tel 760 598 9899 www texmate com THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 6: ...ezel diagram Annunciator LEDs The annunciator LEDs can be programmed to indicate the alarm status Setpoint 1 can be configured to indicate the rising signal trend Setpoint 2 can be configured to indicate the falling signal trend They are labeled from left to right SP1 SP2 SP3 SP4 SP5 SP6 See Display with Faceplate and Bezel diagram Program Lockout Switch When the PROGRAM LOCKOUT switch is set to p...

Страница 7: ... 1XX Reset counters CH1 CH2 CH3 CH4 total 1 and total 2 at power up 2XX Reset total 1 and total 2 at power up 3XX Capture Pin When the CAPTURE pin pin 22 is connected to the COMMON pin pin 21 the CAPTURE pin can be programmed for setpoint relay activation or macro control applications in the setpoint control settings mode of the setpoint programming mode SPC_X X2X Common Pin To activate the LOCK H...

Страница 8: ...function being explained or more than one choice can be made SP1 SP2 SP3 SP4 SP5 SP6 Prog Where a left and right hand are shown on separate buttons on the same diagram this indicates that the buttons must be pressed at the same time The exceptions to this rule are when carrying out the Model and Software Code Version Check or the Code Blanking and Macro Check Programming procedures are graphic bas...

Страница 9: ...point Programming Mode The setpoint programming mode provides access to program all setpoint and relay functions Code 10 Bargraph Setup Cod10 Code 10 applies to Tiger 320 Series meters with bargraph displays only See data sheets for DI 50EB51 DI 50TB51 FI B101D50E and FI B101D50T SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display P SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display P P P P P P P P P P...

Страница 10: ...wing selected on demand modes Tare Single point calibration Two point calibration Primary input compensation Manual loader manual offset Print CH3 SP_1 SP_3 SP_5 PEAK TOT_1 CH1 To view press the button SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display Press 1 View Mode CH4 SP_2 SP_4 SP_6 VALEY TOT_2 CH2 To view press the button On Demand Modes The meter can be programmed to activate the following f...

Страница 11: ...tware CodeVersion Check The meter model and software code version number can be checked at any time while in the operational display using the following procedure Before configuring the meter carry out the following meter configuration checks Model and software code version check Code blanking and macro check After powering up the meter check the model and software code version number and note thi...

Страница 12: ...d when entering the main programming mode It allows you to adjust the brightness of the display LEDs and setpoint annunciators without interfer ing with other configuration settings It is always available even with the PROGRAM LOCK switch set to ON or the external LOCK pin connected to the COMMON pin locking out the programming modes The display brightness can be set between 0 and 7 with 0 being d...

Страница 13: ...input source 4 Calibrate Smart Input Module Note This function is not available on all input modules 5 Calibrate Analog Output requires multimeter con nected to pins 16 and 17 6 7 0 Set Serial Communications Properties 1 Set Auto Zero Maintenance for 3rd digit 2 Set Averaging Samples Averaging Window for 3rd digit 3 Totalizer Settings Mode 4 Setup 32 point Linearization Tables 5 Scale Analog Outpu...

Страница 14: ...m 1 to 255 samples The averaging window can be set to between 1 and 65535 counts See the calibration modes diagram on Page 13 showing a breakdown of 1st 2nd and 3rd digits See Input Signal Sampling Showing Averaging Window dia gram opposite Example Procedure The example procedure on Page 16 shows how to configure channel 1 CH1 with an averaging sample rate of 10 counts and an averaging window of 1...

Страница 15: ...P1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Example SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 1 SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 1 SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog OR SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog OR OR ...

Страница 16: ...el 1 for 2nd digit Enter the Averaging Sampling Rate Mode Pass Brightness Mode and enter Calibration Mode Step 4 Step 5 Step 3 Step 1 Step 2 Operational Display Enter Brightness Mode Step 6 To Step 7 SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 1 SP1 SP2 SP3 SP4 SP5 SP6 Prog Press at same time Press at same time SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 1 SP1 SP2 SP3 SP4 SP5 SP6 Prog S...

Страница 17: ...splay Format sub menu Selecting X7X enters the Last Digit Text Character sub menu CODE 1 Display Configuration Modes All meter display modes except the display brightness mode are configured in Code 1 See diagram below See Code 1 diagram on Page 18 for a breakdown of 1st 2nd and 3rd digits settings Data Source 2nd Digit X5X The data source for the primary display is configured by selecting 5 in th...

Страница 18: ...ts See Analog Output Supplement for further details Note 1 LED annunciators are always off except when the meter is in single channel VOLTAGE or CURRENT mode and Code 3 X6X or Code 7 X6X in which case the LEDs indicate which 32 point table has been selected from the rear pins SP1 Table 1 SP2 Table 2 SP3 Table 3 SP4 Table 4 Note 2 These options are only for use with meters that have more than one d...

Страница 19: ... OR Step 4 Press at same time Press at same time Step 6 0 Primary Display 1 Second Display See Note 2 Third Display See Note 3 Peak Valley 4 Analog Output 1 5 Analog Output 2 6 Totalizer 1 7 Totalizer 2 OR OR Step 7 Step 8 Step 9 Press 1 Press 1 From Step 5 Step 5 Select diSP as the Data Source from the options listed in the Select Data Source diagram below CONFIGURING THE DATA SOURCE PROCEDURE Se...

Страница 20: ... point Enter the Display format Mode SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog X SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog X SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3...

Страница 21: ...P3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog X SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Step 1 Step 2 Set Code to X71 1st Digit X Not relevant 2nd Digit 7 Selects text character mode 3rd Digit 1 Selects channel 1 Step 3 Operational Di...

Страница 22: ...g SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Step 1 Step 2 Step 3 SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display Press 2 Press 1 OR Step 4 Enter Brightness Mode Pass Brightness and Calibration Modes and enter Code 1 Press at same time Press at same time Press at same time Press at same time CONFIGURE SET...

Страница 23: ...7 Internal 24 hour clock ANALOG SAMPLE RATE MEASUREMENT TASK 0 Voltage Current 1 TC 3rd digit selects type of TC 2 RTD 3 wire 3rd digit selects type of RTD 3 RTD 2 or 4 wire 3rd digit selects type of RTD 4 Frequency 5 Period 6 Counter 7 Smart Input Module CODE 2 CHANNEL 1 MEASUREMENT TASK AND SAMPLING RATE SMART INPUT MODULE 0 Output Register 1 1 Output Register 2 2 Output Register 3 3 Output Regi...

Страница 24: ...2 point Linearization on CH1 Tables 1 to 4 selected from the rear pins of selected input modules The selected table is not available if CH2 CH3 or CH4 is oper ating in the analog output mode CH1 must be set to Voltage Current in Code 2 X0X See Note 5 7 Note All linearization tables are set up in the Calibration Mode 24X SERIAL MODE 0 ASCII Mode 1 Modbus Mode 2 Master mode used to cus tomize print ...

Страница 25: ...OINT LINEARIZATION FOR THERMOCOUPLE 0 Type J 1 Type K 2 Type R 3 Type S 4 Type T 5 Type B 6 Type N 7 Select user defined table set up in CAL 24X FOR RTD TYPE 3 WIRE 0 Resistance 1 RTD 385 2 RTD 392 3 RTD 120 4 Cn10 DIGITAL INPUT 0 Frequency 99 999 Hz range from 0 01 Hz 1 Frequency 999 99 Hz range from 0 01 Hz 2 Frequency 99 999 kHz range from 1 Hz 1 s gate 3 Frequency 500 kHz range from 10 Hz 0 1 ...

Страница 26: ...ns available for Channel 3 When a triple input signal con ditioner is installed the third input signal is processed and displayed on CH3 Post processing and measure ment task functions for CH3 are configured in the 1st 2nd and 3rd digits of Code 5 The diagram opposite lists the avail able configuration selections in Code 5 Example Procedure Configure CH3 to display the square root of a voltage inp...

Страница 27: ...E 0 Type J 1 Type K 2 Type R 3 Type S 4 Type T 5 Type B 6 Type N 7 Select user defined lineariza tion table Table 1 set up in CAL 24X FOR RTD TYPE 2 3 4 WIRE 0 Resistance 1 RTD 385 2 RTD 392 3 RTD 120 4 Cn 10 MEASUREMENT TASK 0 No Function 1 Voltage Current 2 TC 3rd digit selects type of TC See Note 7 3 RTD 3rd digit selects type of RTD See Note 7 4 Real Time Clock and Timer 3rd digit selects type...

Страница 28: ... 2 See Note 5 3 32 point Linearization on Result using Table 3 See Note 5 4 32 point Linearization on Result using Table 4 See Note 5 5 125 point Linearization on Result Tables 1 to 4 cascaded See Note 5 6 32 point Linearization on Result Tables 1 to 4 selected from the rear of the meter The selected table is not available if CH2 CH3 or CH4 is operating in the analog mode CH1 must be set to Voltag...

Страница 29: ... stamp format 3 Hrs Min Sec with CR LF 4 Spreadsheet Format No time stamp with print log 5 Spreadsheet Format Time stamp format 1 Mth Day Yr Hrs Min Sec 6 Spreadsheet Format Time stamp format 2 Day Mth Yr Hrs Min Sec 7 Spreadsheet Format Time stamp format 3 Hrs Min Sec ALL ABOVE ARE REAL TIME CLOCK OPTIONS LOG OR PRINT TRIGGER 0 No trigger 1 Trigger on Demand from PROGRAM Button 2 Trigger on Deman...

Страница 30: ...ally programmed Setpoint acti vation values can be set within the total span range of the meter and the selected input module Setpoint and Relay Control Settings See the Setpoint and Relay Control Settings diagram on Pages 34 and 35 The control settings provide access to the following setpoint and relay func tions for configuration using the meter s 1st 2nd and 3rd digits 1st Digit Relay Energize ...

Страница 31: ... MAKE BREAK EDGE EVERY SAMPLE PERIOD OFF LATCH ON LATCH SP RESET Setpoint Latching Setpoints can be programmed in relay latching modes Setpoint Reset Trigger Setpoints can be programmed to reset selected registers or be manually reset They can also trigger a data print or a data log DUAL PID SP PID Control Settings The PID proportional integral derivative control function pro vides exceptional con...

Страница 32: ...N Pulsed OFF Modes These are delay modes were the relay is normally on and pulses off when the setpoint activates 1 Shot OFF mode Programmable Minimum OFF time SP OFF SP ON 1 Shot OFF Mode Prog Min OFF time Adj MIN OFF T RLY ON RLY OFF Adj DOB Single actuation pro grammable minimum off time and DOB set tings Pulse OFF mode Programmable OFF time Repeat OFF Mode Multiple actuation programmable off a...

Страница 33: ...isplay SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 6 SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 1 OR Step 4 Press at same time Press at same time SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Operational Display SP1 SP2 SP3 SP4 SP5 SP6 Prog SP1 SP2 SP3 SP4 SP5 SP6 Prog Press 1 SP1 SP2 SP3...

Страница 34: ...t value with FALLING INPUT SIGNAL INITIAL START UP INHIBIT 3 Energized BELOW setpoint value with RISING INPUT SIGNAL INITIAL START UP INHIBIT SP Activation Source 0 Activate Setpoint Source from Selected Register 1 Select Source for Setpoint Note X1X is a register selection procedure only To finish reset to X0X to activate the selection or reset to 2 7 as required for digital input selection 2 Dig...

Страница 35: ... Third digit set to XX6 Delay on make DOM time 0 0 to 6553 5 secs Delay on break DOB time 0 0 to 6553 5 secs Reset SPC_X to XX0 DOM 0 0 to 6553 5 secs Minimum on time M_on 0 0 to 6553 5 secs On time on _t 0 0 0 001 to 6553 5 65 535 secs On time on _t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 to 6553 5 secs Off time oFF_t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 0 001 to 6553 5 65 535 secs On time on ...

Страница 36: ...et hold the button down while cycling through the decades and release it when oFF or tArE appears Registers that Should Not be Used The following registers are contained within the selectable 1 to 244 Register Set but they should not be selected because they are either reserved for future use or for use by the operating system only 15 38 47 48 52 53 61 64 123 128 140 141 234 244 Any selection of t...

Страница 37: ...puts Input Signal Pins 1 to 6 See the I Series Input Modules Guide Z87 for connection details of all input modules On most single input signal conditioners usually Pin 1 is the signal high pin Hi and Pin 3 is the signal low pin Lo Function Pins Pins 18 to 22 Pin 18 Program Lock By connecting the PROGRAM LOCK pin to the COMMON pin pin 11 on the main PCB the PROGRAM LOCK pin allows the meter s progr...

Страница 38: ...lay Modules with up to 4 Independent 300V 210mA DC only SSRs 35 34 33 31 32 30 29 28 SP3 SP2 SP1 SP4 Order Code OR71 Options SP1 SP2 SP3 SP4 SP5 SP6 0 to 5V 0 to 5V 0 to 5V 0 to 5V 0 to 5V 0 to 5V TTL 5VDC Output 50 mA SP3 SP2 SP1 SP4 SP5 SP6 Comm Comm 35 34 33 31 32 30 29 28 Order Code NPN Open Collector Max 50V 100mA Sink Source OR81 OR82 Options Setpoint MACRO Setpoint Logic Input 6 Outputs 6 O...

Страница 39: ...e Simply order the input and output options to suit your application Input Signal Conditioning Modules Standard Serial Output Carrier Board Serial Output Modules Analog Output Modules Power Supply standard or optional low voltage Processor Display red green or super bright red LEDs 320 Series Base Meter 0 20 mA 0 10 VDC Dual 0 10 VDC Select from over 120 single dual triple or quad inputs covering ...

Страница 40: ...Module Ordered Separately RS 232 Output Module PCB RS 485 Output Module PCB Note Externally mounted Ethernet compatible communication output modules are available that connect directly to the standard RS 232 RS 485 serial module outputs Standard Serial Output Modules RS 232 or RS 485 Component Layout and External Devices continued Analog Output Module PCB Current or Voltage Selection Header CURREN...

Страница 41: ...noisy components Shielding cables for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconnect power to the meter The breaker switch should be in close proximity to the meter and marked as the disconnecting device for the meter or meter circuit The circuit breaker or wall switch must be rate...

Страница 42: ...3 Code 3 Channel 1 Post Processing and Serial Mode Functions 24 Code 4 Channel 2 Measurement Task and Sampling Rate 25 Code 5 Channel 3 Functions 26 Code 6 Channel 4 Functions 27 Code 7 Result Processing 28 Code 8 Data Logging Print Mode 29 Code 9 Functions for Digital Input Pins 29 Code Blanking 11 12 Clock Timer Configuration 23 26 27 Real time Clock Configuration 23 26 27 Real time Clock Date 2...

Страница 43: ...d Not Be Selected 36 Resetting and Incrementing Using Setpoints 36 Relay Logic Output Modules 38 Serial Communication Configuration 24 Pinouts 38 Setpoint Programming Mode 30 35 Data Logging 31 Data Printing to PC 31 Data Printing to Serial Printer 31 Display Flashing 31 Hysteresis or Deviation 31 32 34 Level 1 Basic Mode Prog Procedures 33 PID Control Settings 31 34 Real time Clock Option 31 Real...

Страница 44: ...replacement or repair at its option at its factory of any of the products which shall within the applicable period after shipment be returned to Texmate s facility transportation charges pre paid and which are after examination disclosed to the sat isfaction of Texmate to be thus defective The warranty shall not apply to any equipment which shall have been repaired or altered except by Texmate or ...

Отзывы: