Initial Setup Procedures
[CodE_4] - Channel 2 Measurement Task & Sampling Rate
0 No user defined Linearization
on CH2
1 32-point Linearization on CH2
using Table 1
2 32-point Linearization on CH2
using Table 2.
See Note 5
3 32-point Linearization on CH2
using Table 3.
See Note 5
4 32-point Linearization on CH2
using Table 4.
See Note 5
5 125-point Linearization on CH2
(Tables 1 to 4 cascaded).
See
Note 5
6 –
7 –
Code 4 is a single code that
combines all the configuration
and post processing functions
available for Channel 2.
When a
dual input
signal con-
ditioner is installed, the second
input signal is processed and
displayed on CH2.
Measurement task and 32-point
linearization for CH2 is config-
ured in the 1st and 2nd digits of
Code 4. The diagram opposite
lists the available configuration
selections in Code 4.
Example Procedure:
Configure CH2 for a direct voltage input with no
linearization
by setting Code 4 to [
010
].
MEASUREMENT TASK
0 Voltage, Current
1 TC (type as per 2nd digit)
2 RTD (type as per 2nd digit)
3 Second Digital Input Channel (type
as per 2nd digit)
FOR VOLTAGE & CURRENT
0 Channel 2 Disabled
1 Direct (no post processing)
2 Square Root of Channel 2
3 Inverse of Channel 2
4 Output Register 1 (smart module)
5 Output Register 2 (smart module)
6 Output Register 3 (smart module)
7 Output Register 4 (smart module)
32-POINT LINEARIZATION FOR CH2
CODE 4 – CHANNEL 2 MEASUREMENT TASK AND 32-POINT LINEARIZATION
FOR THERMOCOUPLE
0 Type J
1 Type K
2 Type R
3 Type S
4 Type T
5 Type B
6 Type N
7 Select user defined table set up in
CAL [24X]
FOR RTD TYPE (3-WIRE)
0 Resistance
1 RTD 385
2 RTD 392
3 RTD 120
4 Cn10
DIGITAL INPUT
0 Frequency - 99.999 Hz range from 0.01
Hz
1 Frequency - 999.99 Hz range from 0.01 Hz
2 Frequency - 99.999 kHz range from 1 Hz
(1 s gate)
3 Frequency - 500 kHz range from 10 Hz
(0.1 s gate)
4 Period - 9.9999 s (100 µs resolution)
5 Period - 999.99 ms (10 µs resolution)
6 Up/Down Counter with Prescaler
7 Set Prescaler
FIRST DIGIT
SECOND DIGIT
THIRD DIGIT
See
I-Series Input Modules Guide (Z87)
for pro-
cedures to set up a dual input module.
Use
buttons to set
prescale values from 1 to
65535 counts
Note 5:
If only 4 kB memory installed, functions
2 to 6 are not available in:
• Code 3 second digit.
• Code 4 third digit.
• Code 7 second digit.
START HERE
Exit Code 5.
Return to
Operational Display
CONFIGURING CH2 MEASUREMENT TASK PROCEDURE
Pass Brightness Mode,
Calibration Mode, and
Codes 1 to 3, and enter
Code 4
Set Code 4 to [010]:
1st Digit = 0 Selects voltage, current
2nd Digit = 3 Selects inverse of CH2
3rd Digit = 0 Selects no linearization
Save CH 2 Measurement
Task setting
To
Step
4
From Step 3
Step 3
Step 1
Step 2
Operational Display
Enter Brightness Mode
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
5
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
at same
time
Press
at same
time
Step 5
Step 4
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Operational Display
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
1
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
OR
Press
at same
time
Press
at same
time
CONFIGURE CH2
MEASUREMENT
TASK
SP1 SP2 SP3 SP4 SP5 SP6
Prog.