[CAL] - Calibration Modes for Input and Output continued
[CAL] - Calibration Modes for Input and Output continued
See
Advanced Calibration & On Demand Mode Supplement
(NZ203)
for further calibration procedures.
Input Signal Filtering and Averaging
Input signal filtering and averaging is configured in the calibra-
tion mode. Programmable averaging allows you to program the
number of samples you want to average the input signal over
(from 1 to 255 samples).
A programmable averaging window provides a quick response
time to large input signal changes. The averaging window can
be set to between 1 and 65535 counts.
Select averaging
sampling rate from
1 to 255 samples
Save averaging
sampling rate setting
and enter the Averaging
Window mode
CONFIGURING AVERAGING SAMPLING & AVERAGING WINDOW PROCEDURE
0 Result
1 Channel 1
2 Channel 2
3 Channel 3
4 Channel 4
Set Calibration Mode to [221]:
1st Digit = 2 Selects related
calibration functions
2nd Digit = 2 Selects averaging
samples for 3rd digit
3rd Digit = 1 Selects channel 1
for 2nd digit
Enter the Averaging
Sampling Rate Mode
Pass Brightness Mode
and enter
Calibration Mode
Step 4
Step 5
Step 3
Step 1
Step 2
Operational Display
Enter Brightness Mode
Step 6
To
Step
7
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
1
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
at same
time
Press
at same
time
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
1
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
OR
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Example
Press
1
Select [000] to
leave the
Calibration Mode
Save settings
Select averaging
window between 1
and 65535 counts
Save averaging
window settings
Exit Code1.
Return to
Operational Display
Step 8
From Step 6
Step 7
Step 10
Step 9
Step 11
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Example
Operational Display
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
OR
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
Press
1
Press
1
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
SP1 SP2 SP3 SP4 SP5 SP6
Prog.
OR
INPUT SIGNAL
FILTERING &
AVERAGING
Press
at same
time
Press
at same
time
OR
Example Procedure:
Select an averaging sampling rate of 10 samples and an aver-
aging window of 1000 counts for Channel 1 by setting [CAL]
to [
221
].
START HERE