battery storage system ts hV 70 outdoor
19
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.B.01 Last revised 01/2021
5.8 CONNECTOR PANEL
Admin Master
Structure
30
31
32
33
34
35
38
37
36
39
30
230 V AC service plugs
31
24 V voltage supply for communication components
32
N conductor terminal block
33
Circuit breakers
34
PE conductor terminal block
35
Surge arrester (for consumer)
36
Network connections (SMA STPS 60, APU HV1000-S)
37
X3/X4 terminals
38
NH00 isolator SMA STPS 60 and consumer
39
X1 through clamps
X3/X4 terminals
37
1
2
3
4
X3: max. 95 mm
2
X4: max. 95 mm
2
1
X3 (+) BatBreaker input terminal to SMA STPS 60 (red)
2
X3 (-) BatBreaker input terminal to SMA STPS 60 (black)
3
X4 (+) APU output terminal to BatBreaker (white)
4
X4 (-) APU output terminal to BatBreaker (blue)
Circuit breakers F3 …F8
1
F3 circuit breaker for heating unit L
2
F3 circuit breaker for heating unit N
3
F4 circuit breaker for air conditioner 1 L
4
F4 circuit breaker for air conditioner 1 N
5
F5 circuit breaker for air conditioner 2 L
6
F5 circuit breaker for air conditioner 2 N
7
F6 RCB / CB service plugs L
8
F6 RCB / CB service plugs N
9
F7 circuit breaker for 24 V voltage supply / IVM
10
F7 spare circuit breaker for router
NH00 isolators F1, F2
38
4
5
6
1
2
3
1
F1 SMA STPS 60 connection L1 (125 A)
2
F1 SMA STPS 60 connection L2 (125 A)
3
F1 SMA STPS 60 connection L3 (125 A)
4
F2 outdoor load (35 A)
5
F2 outdoor L2 load (35 A)
6
F2 outdoor L3 load (35 A)
X1 through clamps
39
1
2
3
4
5
6
7
8
9
X1: max. 50 mm²
1
AC connecting terminal L1
2
AC connecting terminal L1
3
AC connecting terminal L2
4
AC connecting terminal L2
5
AC connecting terminal L3
6
AC connecting terminal L3
7
AC connecting terminal N
8
AC connecting terminal N
9
AC connecting terminal PE
33
1 2 3 4 5 6 7 8 9 10
Содержание TS HV70 Outdoor
Страница 1: ...LITHIUM STORAGE SYSTEM TS HV70OUTDOOR Installation and Operating Manual ...