teChnICal data
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.B.01 Last revised 01/2021
4 TECHNICAL DATA
4.1 BATTERY CABINET SMA SUNNY TRIPOWER STORAGE 60 (SMA STPS 60)
The battery storage system TESVOLT TS HV 70 Outdoor has been optimised for use with the
SMA STPS 60 three-phase battery inverter. The overall system is perfectly coordinated to the needs of
trade and industry. The battery storage system can be used for an extremely wide range of applica-
tions thanks to the flexible energy management provided by the SMA Inverter Manager and the high
C-rate of the TESVOLT battery storage system. Projects up to the megawatt range can be implemented
with this unit.
TECHNICAL DATA SMA STPS 60
Nominal charging power (AC)
60 kVA
Nominal discharging power (AC)
75 kVA
DC voltage range
575 to 1,000 V
Dimensions (H x W x D)
740 x 570 x 306 mm
Max. efficiency
98.8 %
Self-consumption
< 3 W
Operating temperature
-25°C to 60°C
Weight
77 kg
Protection class
IP 65 | NEMA 3R
Communication
Modbus TCP/IP
Topology
Transformer-free
Guarantee
5 years
Figure 4.1 SMA STPS 60 with SMA Inverter Manager
4.2 TESVOLT TS HV 70 OUTDOOR
TESVOLT TS HV 70 OUTDOOR TECHNICAL DATA
Energy (14 | 16 battery modules)
67 kWh | 76 kWh
C-rate
1C
Cell
Lithium NMC prismatic (Samsung SDI)
Max. charging/discharging current
94 A
Cell balancing
Active Battery Optimizer
Cycles expected at 100 % DoD | 70 % EoL | 23°C +/- 5°C
6,000 (1C/1C) or 8,000 (0.5 C/0.5C)
Efficiency (battery)
Up to 98 %
Self-consumption (standby)
5 W (without battery inverter)
Operating voltage
666 V to 930 V
Ambient temperature
-33°C to 55°C
1, 2
Humidity
< 85 % (non-condensing)
Altitude of installation site
< 2,000 m above sea level
Weight
Total
< 1,020 kg | 1,101 kg
1
Battery module
36 kg
Battery cabinet
< 280 kg
1
Dimensions (H x W x D)
1,945 x 1,989 x 1,030 mm
1
Certificates/standards
Cell
IEC 62619, UL 1642, UN 38.3
Battery module
CE, UN 38.3, IEC 62619, IEC 61000-6-1/2/3/4, German Battery Act 2006/66/EC
Battery cabinet
DIN EN 62208, DIN EN 62368-1, DIN EN 60950-1, DIN EN 61439,
IEC 62262-IK10 GR-487-CORE, R3-40/41/42/43/44/59/192/204/207
Guarantee
10-year performance guarantee, 5-year system guarantee
Recycling
TESVOLT offers free return of batteries from Germany
Protection class
IP 55, NEMA 3/3R
Battery specification as per DIN EN 62620:2015
IMP47/175/127/[14S]E/-20+60/90
1
Depending on design |
2
SMA STPS 60: -25°C to 60°C