34
ConneCtIon to the battery InVerter
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.B.01 Last revised 01/2021
Battery inverter SMA STPS 60 connection diagram
WARNING! Possible damage to the battery storage system
Before connecting the battery inverter, the installation of the battery storage system must be com-
pletely finished.
DANGER! Lethal electric shock or damage to the battery storage system due to incorrect connection
The current installation manual from the manufacturer SMA must be followed for the correct
connection of the battery inverter. For this reason, the information provided in this manual is entirely
non-binding.
BATTERY
CHARGER
E
F
D
C
B
A
LAN 2
Switch
LAN 1
Switch
Power Measurement
(Janitza UMG 604/605)
LCS Tool
SMA Data
Manager M
SMA
Inverter Manager
Master/slave systems
In master/slave systems, the TS HV 70 Outdoor’s
DC connection on the SMA STPS 60 is
established using a BatBreaker.
TS HV 70 OUTDOOR
SMA STPS 60 BatBreaker
ITEM DESIGNATION
DESCRIPTION
A
AC connection terminals
Tightening torque 20 Nm
B
Grounding cable / unit grounding
Tightening torque 3.9 Nm
C
AC surge protection
Surge Protection Device SPD
D
DC surge protection
Surge Protection Device SPD
E
DC connection terminals
Connection of the battery storage system: The tightening torque is 20 Nm.
F
Two ethernet interfaces
Communication interface to the SMA Inverter Manager
STOP