ConneCtIon to the sma sunny trIpower storage 60
© TESVOLT We reserve the right to make technical changes! RD.TI.026.E.ENG_Installation_Manual_TSHV70OD_v.A.01 Last revised
07/2020
SMA STPS 60 connection diagram
ATTENTION! Possible damage to the TS HV 70 Outdoor.
Installation of the storage system must be complete before the SMA STPS 60 is connected.
DANGER! Lethal electric shock or damage to the unit due to incorrect connection.
The valid installation manual for the SMA STPS 60 provides authoritative information about correctly con-
necting the SMA STPS 60. For this reason, the information provided in this manual is entirely non-binding.
BATTERY
CHARGER
E
F
D
C
B
A
LAN 2
Switch
LAN 1
Switch
Power Measurement
(Janitza UMG 604/605)
LCS Tool
SMA Data
Manager M
SMA
Inverter Manager
Master/slave systems
In master/slave systems, the TS HV 70’s
DC connection on the SMA STPS 60 is
established using a BatBreaker.
TS HV 70 OUTDOOR
SMA STPS 60 BatBreaker
ITEM DESIGNATION
DESCRIPTION
A
AC connection terminals
Tightening torque 20 Nm
B
Grounding cable / unit grounding
Tightening torque 3.9 Nm
C
AC surge protection
Surge Protection Device SPD
D
DC surge protection
Surge Protection Device SPD
E
DC connection terminals
Battery connection: tightening torque 20 Nm
F
Two ethernet interfaces
Communication interface to the SMA Inverter Manager
Connecting the SMA STPS 60
1
Unlock the lock on the cover
I
with a key
T
and remove the
cover.
STOP